46
HE 5760 Operating Instructions
# 372449| Version 3.2
10.2.4 Valve error
Display
Criterion
Cause / Remedy
Ch.
3 Valve 1
Wire
breakage
Output is monitored:
Open valve outlet
Valve not connected
Valve defective
Ch.
3 Valve 2
Overcurrent Output is monitored: Short
circuit at the valve outlet
Line squeezed
Valve defective
Ch. 3 Valve 3 does not
open
No short-term pressure drop in
the local pressure tank
Valve defective
Value for pressure
drop too high
Ch. 3 Valve 4 does not
close
No short-term pressure
increase in the local pressure
tank
Valve defective
Value for pressure rise
too high
Ch. 3 Valve 5 no pressure Tank pressure has not
recovered within the tank refill
time
Valve defective
Tank refill time too low
System pressure too
low
10.2.5 Valve control tank pressure sensor error
Display
Criterion
Cause / Remedy
Ch. 4 Tank Pressure 1
Sensor Malfunction
Input is monitored:
Open sensor input
Power interruption
Sensor not connected
Pressure sensor
defective
Ch. 4 Tank pressure 4
Sensor closure
Input is monitored: short-
circuited sensor input
Line squeezed
Pressure sensor
defective
10.2.6 Valve control Tank pressure error (sensor is OK)
Display
Criterion
Cause / Remedy
Ch.
7 Tank pressure
1
low (Tank 1-4)
Pressure value lower than
specified with tank pressure
monitor
System pressure
missing
Value set too high