9.1
Parameter Table
Sensor Min. = Base measuring range start
Sensor Max. = Base measuring range end
Note!
The base measuring range is to be taken from the nameplate!
Note!
Please note that, when setting the measuring range start and end, the
difference between the two must not be less than 25% of the base
measuring range!
Parameter
Adjustment range
Factory Setting
Unit
Input signal
Damping (time constant T)
The damping is
implemented as a first-
order low-pass.
It affects the measured
value and stabilizes a
fluctuating input signal (
see
Approx. 99 % of the end
value are reached, after the
fivefold time, set via the
parameter ‘Damping’ (
see
The higher the damping
value, the slower does the
output signal respond.
0.00…60.00
2
s
Offset
This parameter can also be
set on the device itself.
(
see chapter 8.1 and
chapter 8.2)
-
10%…+10% from
base measuring
range end
0.00
mbar
Measuring range start
The measuring range start
indicates the pressure at
which an output signal of
0% is displayed.
Sensor
Min…Sensor Max
Base measuring range start
Measuring range end
The measuring range end
indicates the pressure at
which an output signal of
100% is displayed.
Sensor
Min…Sensor Max
Base measuring range end