Herz STOCKHOLM Скачать руководство пользователя страница 1

HERZ HIU STOCKHOLM 

 

 

Page 1 

HERZ Heat Interface Unit 

HIU STOCKHOLM 

Instruction for operators and plumbers

,

 Issue 0419 

 

 

 

Description 

The HERZ Stockholm Heat Interface Unit (HIU) provides domestic hot water and space heating to 
properties that are serviced from district heating or central boiler plants. The HIU comprises of two 
heat exchangers, one for the DHW providing instant hot water at a safe regulated temperature and the 
second for the space heating. The HIU is indirect so the primary heating circuit is hydraulically 
separated from the property space heating by the second plate heat exchanger. 
Pipe connection to an HIU is realised by means of ball valves. Connection of the pipe work with the 
HIU is possible from the floor or from the top with a separate top entry bracket. 
 
Main Features: 

 

Instantaneous hot water and space heating to properties 

 

Twin heat exchangers provide hydraulic separation  

 

Thermostatic hot water temperature control  

 

Tempering valve to prevent risk of scalding 

 

Pressure temperature control valve allows DHW heat exchanger to operate on demand only 

 

Hot water priority valve maximises primary flow to DHW heat exchanger by stopping the 
supply to the space heating heat exchanger when a hot tap is opened 

 

”Summer bypass” valve maintains a minimum primary temperature when space heating is not 
in use 

 

Low primary return temperature maximises system efficiency 

 

Suitable for radiators heating 

 

Primary Return with Differential Pressure Control Valve 

 

110mm Spool piece provided for water meter 

 

18mm stainless steel pipe work 

 

Strainer with fine-mesh screen in primary flow 

 

Strainer with fine-mesh screen in return flow of space heating circuit 

 

Strainer with fine-mesh screen in cold water inlet 

 

 

 

1 4023 40-061_V05

 

Содержание STOCKHOLM

Страница 1: ...entry bracket Main Features Instantaneous hot water and space heating to properties Twin heat exchangers provide hydraulic separation Thermostatic hot water temperature control Tempering valve to prevent risk of scalding Pressure temperature control valve allows DHW heat exchanger to operate on demand only Hot water priority valve maximises primary flow to DHW heat exchanger by stopping the supply...

Страница 2: ...tem The user must not make any technical changes to the HIU Otherwise HERZ will not assume liability for any resulting damage The unit must be filled with water containing the correct amount of inhibitor failure to do so will invalidate the warranty If the property is to be left unoccupied for a prolonged period it is recommended that the HIU domestic pipe work is isolated and drained Risk of elec...

Страница 3: ...ed loose fit the ball valves to the relevant pipes before tightening to the HIU Tighten the ball valve connections or fit the respective pipe work to the ball valves and tighten the compression connections Please ensure the ball valves are level before the HIU is fully securing to the wall Please note that the unit will be delivered with the cables are disconnected inside the terminal box this is ...

Страница 4: ...valve is obligatory safety regulation In HIU Stockholm this valve is integrated into pre mounting unit Position 1 If pre mounting unit is not included into delivery domestic water safety valve with integrated check valve has to be installed separately order number 1 4023 44 in pipeline as shown on picture above Position 2 ...

Страница 5: ...it is achieved However thermo siphon units have to be filled with prepared frost protected heat transfer medium If antifreeze agents must be filled in so far non frost protected heating systems the following points must be observed 1 It must be ensured that the appropriate sealing materials are used 2 The system should be flushed carefully 3 After filling the system with antifreeze extra attention...

Страница 6: ...get operated for several days When draining the substation a vessel with a capacity of 4 8 litres should be placed under the substation and the hot water from the ball valves should be tapped until the substation is completely emptied If there is a risk of frost it should be noted that not only the water in the transfer station and in the hot water pipes can freeze but also in all cold water suppl...

Страница 7: ... a prolonged period of time as this would make the system more susceptible to corrosion Component servicing In hard water areas lime scale can build up in the system Depending on the hardness of the water the unit should be de scaled by a professional every one to two years If lime scale build up in the system is excessive some of the valves could be damaged these should be replaced immediately to...

Страница 8: ... the domestic hot water Undo the connection nuts and remove the valve check the non return valves and strainer gaskets clean or replace if necessary Component replacement Drain the domestic hot water and replace the valve and strainer gaskets Differential Pressure Control Valve Routine servicing Check all connection seals Component replacement Drain the primary undo the capillary retaining nut and...

Страница 9: ...nsion vessel is not maintaining pressure and needs replacing Component replacement Drain the secondary side of the unit and undo the capillary nut using two spanners undo the connection nut and remove the expansion vessel by lifting up to clear the bracket and slide down and out to remove Replace in the same way in reverse then refit the connection nut and capillary nut Refill the secondary system...

Страница 10: ...oblems with hot water Long wait for hot water at the tap Check the bypass circuit Check the primary heating circuit Pressure temperature controller is leaking Replace the Pressure temperature controller Pressure temperature controller sticks Replace the Pressure temperature controller Temperature of the hot water is too low Increase the flow temperature on the heat source Check the valves settings...

Страница 11: ...ic water 8 Differential pressure control valve 9 Heat exchanger domestic water 10 Heat exchanger heating 11 Manual air vent 12 Ball valve with non return function 13 Safety valve 14 Pump 15 Expansion vessel 16 Controller 17 Contact sensor 18 Outdoor sensor 19 Actuating drive 20 Control valve 21 Spacing piece for heat meter 110mm G3 4 flat sealing Sensor can be fitted at primary strainer pos 6 Adap...

Страница 12: ...a specialist depending on the hardness level of the water every one or two years If the calcification affects the valves too much they should be exchanged immediately to ensure a flawless function Do not use abrasive or aggressive cleaning agents to clean the units It is recommended to clean with a damp cloth in addition with a few drops of a liquid household cleaner Furthermore the quality of the...

Страница 13: ...4 hours 0 Chlorides Cl 100 100 200 200 300 300 no limit 0 Free chlorine Cl2 1 1 5 5 within 5 hours 0 0 hydrogen sulphide H2S 0 05 0 05 no limit 0 free aggressive carbon dioxide CO2 5 5 20 20 no limit 0 total hardness dH 4 0 8 5 no limit Nitrate 1 NO3 100 100 no limit 0 Iron 3 Fe 0 2 0 2 no limit 0 Aluminium Al 0 2 0 2 no limit 0 Manganese 3 Mn 0 1 0 1 no limit 0 1 Sulphates und nitrates act as inh...

Страница 14: ... differential pressure generated by the pump is controlled at the respective differential pressure set point This type of control is particularly suitable for heating systems with radiators since the flow noise at the thermostatic valves is reduced Invariable differential pressure Δp c The set point of the differential pressure H is kept constant at the set differential pressure set point above th...

Страница 15: ...en actuator HERZ Motor Valve Drive is controlled via two electric connections L1 1 open and L1 2 close realizing the desired movement direction of the motor This moves the valve pressure plate in the desired direction for opening or closing If the control signal L1 1 open is applied the valve opens The control signal L1 2 close closes the valve After reaching the final stop resp the closing positi...

Страница 16: ...mA Stroke max 8 5 mm minus 0 5 mm over elevation Actuating force 200 N 10 Actuating time 30 s mm Fluid temperature 0 C to 100 C 1 Storage temperature 20 C to 70 C Ambient temperature 0 C to 50 C Degree of protection Protection class IP 54 2 II CE conformity according to EN 60730 Housing material colour Polyamide white Housing cover material colour Polycarbonate transparent Connection cable colour ...

Страница 17: ...Power supply voltage It may only be installed by suitably trained personnel All applicable legal or institutional installation regulations must be complied with The actuator must be protected against moisture It is not suitable for use in outdoor applications Check that the strain relief of the cable in the actuator housing functions correctly The device may only be opened at the factory It does n...

Страница 18: ... in F 100 controller based on the outdoor tempera ture The heat curve relation between outdoor temperature and desired flow temperature is set by means of parameters The motorised control valve is opened gradually when the temperature is lower than the desired flow temperature and vice versa Parameter Channel Tf max Max Flow Temp 1 To min Min Outdoor Temp 2 Tf min Min Flow Temp 3 To max Max Outdoo...

Страница 19: ...for HEATING the motorized control valve is closed and circulation pump is OFF FEATURES Built in LCD alphanumerical display 2 rows of 16 characters with backlighting Easy operator guidance with 5 buttons called M S F 4 analogue inputs PT 1000 sensor 4 digital outputs for motorised valve control The application parameters are stored in the controller and are not affected by a power break The enclosu...

Страница 20: ... 30 C 9 P band 1 01 15 10 l time 55 10 240 sec 11 Correction outdoor temp 0 5 5 C 12 Correction flow temp 0 5 5 C 13 Room thermostat No No Yes Value of the selected parameter can be changed by holding down S and pressing the key for increase or press for decrease value Releasing the buttons with all the parameters are entered into memory that stores the set values TECHNICAL SPECIFICATIONS SAFETY I...

Страница 21: ...lean from all materials to avoid anything preventing the unit from operating correctly Do not use damaged components for assembly Recycling and disposal The substation as well as its transport packaging consists of mostly recyclable resources Device Your substation as well as any accessories does not belong in the household waste Ensure that your device and any accessories get disposed properly Pa...

Страница 22: ...HERZ HIU STOCKHOLM Page 22 ...

Страница 23: ...HERZ HIU STOCKHOLM Page 23 Dimensions for Cover ...

Страница 24: ...HERZ HIU STOCKHOLM Page 24 ...

Страница 25: ...to the Installation Maintenance and Operating manual provided with this unit for full servicing procedures List of components to be serviced regularly and servicing intervals A Service every year B Service every 2 years Pressure temperature control valve Domestic hot water heat exchanger Thermostatic bypass valve Space heating heat exchanger Zone valve Pressure gauge Actuating drive Ball valves Te...

Страница 26: ...nical specifications and or its functioning according to technological progress and requirements It is understood that all images of Herz products are symbolic representations and therefore may visually differ from the actual product Colours may differ due to printing technology used Country specific product deviations are possible Modifications of technical specifications and functions are reserv...