HERZ Roomtemperature thermostat

parameter

advanced installation menu

Number

Description

Description of the values

Factory settings 

other Possibilities

24

RecS - - -

View of the measured values of 

the floor sensor connected to the 

receiver.

“- -.- “

25

FL.Lo - - -

Lower limit of the floor temperature

„No

The lower limitation is 

not used.

From 5 °C to

„FL.Hi“

26

FL.Hi - - -

Upper limit of the floor 

temperature.

„No“

The upper limitation is 

not used

From 

„FL.Lo“

 to 

40 °C

27

reg - - -

Selection of regulation type

„bp“

Proportional band 

(PWM)

„hys“

Hysteresis (On/Off)

28

Bp1 - - -

Screed choice.

„uf1“

For liquid screed with 

low thickness

< 6cm

„uf2“

For traditional 

screed with 

thickness

> 6cm

29

Bp2 - - -

Floor covering choice.

„Fl1“

For tiles

„Fl2“

For wood parquet 

(floating or not)

30

wir

Pilot wire function for French 

Market application:

Use this option if your installation 

has the pilot wire installed in 

combination with an energy saver.

„Yes“

Function activated

„No“

Function 

deactivated

31

min

Minimal value of the setting range

„5,0 °C“

„15,0 °C“

32

max

Maximal value of the setting range

„20,0 °C“

„37,0 °C“

33

Win

Automatic open window detection.

(See user guide for more 

explanation)

„Yes“

Function activated

„No“

Function 

deactivated

34

Clr EEp

All parameters will be reloaded 

with the factory value.

Press on the 

(OK)

 key during few seconds

35

End

To exit the installer’s menu

Press on the 

(OK)

 to exit.

Содержание 1 7795 01

Страница 1: ...ed for safety reasons The maintenance has to be performed by service companies or the manufacturer only The functionality of the controller depends on the model and equipment This installation leaflet is part of the product and has to be obtained Application The thermostats 1 7795 01 and 3 F792 00 are developed to control and manage all type of electrical heating systems or materials The controlle...

Страница 2: ...asy creation of programms weekprogramming in steps of 30 minutes function temporary deactivation of the programm Anti freeze function Holiday or visit function EEPROM non volatile memory 2 AAA batteries up to 2 years operating time 2 parameter menus user and installer In option External sensor with several possibilities of regulation Floor combined HERZ Digital clock with 7 day program datasheet 1...

Страница 3: ...imitation Only available with receiver 6 Heating demand indication 7 Low batteries indicator 8 C or F unit indicator 9 Setting or measured temperature if 5 is displayed Parameter value if 4 is displayed 10 Temporary override function activated 11 Time or parameter title if 4 is displayed 12 Program of the current day the current time bar blinks 13 Pictogram for program creation program state in no...

Страница 4: ...tics Proportional Band PWM 2 K 10min or Hysteresis 0 5 K Swichting contact potential free max 3A 250V AC Power supply Operating life 2x AAA LR03 1 5V Alkalie 2 years Sensing elements Internal External option NTC 10 kΩ at 25 C Softwareversion Showed in parameter menu VERS xxx compatible receivers Flush type Wall type Plus type Standards and homologation Your thermostat has been designed in comformi...

Страница 5: ...an adjust it with the and keys once the value is chosen confirm it with the OK key The thermostat will jump automatically to the next value Note You can always come back to the previous value by pressing the escape key List of the order time and date adjustments Time and day Adjustment of the hours Adjustment of the minutes Adjustment of the day 1 Monday Date Adjustment of the day number Adjustmen...

Страница 6: ... programm P1 Monday to Friday Saturday to Sunday Note You can customise your program as you want See the next part Working mode definition for more explanations Note At any time when the backlight is extinct press the OK key to lit up the backlight and then press another time the OK key to show the current setting temperature Actual value Actual status Program ...

Страница 7: ...rt setting temperature will be followed all the time By pressing or keys the comfort setting temperature starts to blink and can be adjusted Manual Mode Eco Manual working mode the reduced setting temperature will be followed at all time By pressing the or key the reduced setting temperature starts to blink and can be adjusted OFF Mode Use this mode if you need to switch off your installation Be c...

Страница 8: ...owing program P1 Morning Evening Weekend P2 Morning Midday Evening Weekend P3 Day Weekend P4 Evening Weekend P5 Morning Evening Bathroom P6 Morning afternoon Weekend P7 7H 19H Office P8 8H 19H Saturday Shop P9 Weekend Secondary house See the next part to view a complete description of the built in program Use the navigation keys or to change the program day displayed Press the OK key to confirm yo...

Страница 9: ... Comfort temperature The comeback hour needs to be adjusted Last step of the day Reduced temperature The sleeping hour need to be adjusted The programm steps have 30 minutes Each time a value or icon blinks you are able to make a choice with or keys once the choice is made press the OK key to jump to the following steps The program creation will always start with the day 1 Monday Once you have pre...

Страница 10: ...on End of the day 2 Ccoice is to choose the leaving icon to add one step to the program during the day When the choice is made press OK to confirm Then you can adjust the hour of this step with or When the step hour is set press OK to jump to the next step You will be directly invited to adjust with or the hour of the comeback step Press OK to confirm and go to the following step ...

Страница 11: ...subsequent days Make the choice between Yes or no with or and confirm your choice with OK If you select no you will be invited to create a program for Tuesday repeat the previous method to built it If you select Yes you will have the possibility to copy the program to the following days on Tuesday on Wednesday up to the last day of the week 7 Sunday When you press OK on the last day 7 Sunday you w...

Страница 12: ...tings in a child room public area To activate the key lock function first press maintained the escape key and then press simultaneously on the edition key The logo will be displayed on the screen Repeat the same procedure to unlock the key board Open window function Conditions of open window detection The thermostat detects an Open window if the displayed temperature internal or ambient sensor dec...

Страница 13: ...eys to enter the real value Then press Ok to confirm The message Yes should be displayed the value will be stored in the internal memory If you need to erase a calibration press on the escape key The old value will be erased and the message No will be displayed Pay attention Only the heating element driven by the thermostat must be used during the complete step of the calibration 05 OutC AMbC FlrC...

Страница 14: ...the batteries is removed Check the batteries orientation Check the capacity of the batteries My Thermostat Led blinks in Red Problem on sensors The logo blinks ambient sensor Contact your installer or seller The logo blinks Floor sensor Check the connection of the sensor on the receiver Disconnect the sensor and check it with an ohmmeter the value must be around 10 kΩ Batterien sind zu schwach The...

Страница 15: ...0 kΩ at 25 C ß 3950 Entrance in the thermostat menu Press 10 sec on the key MOdE Hot In order to enter in the menu press on the escape key during 10 seconds the following display with the first parameter appears With the and it is possible to change between the Hot Mode and the CLd Mode MOdE Hot MOdE CLd ...

Страница 16: ... modify and confirm by pushing the OK key To leave the parameter menu go to the parameter End and press the OK key Parameters Installer s advanced menu Number Description Description of the parameters Factory value Other possibility 21 Hot Use this option if you want to allow the zone to work in cooling mode Hot Function activated Cld Function deactivated ...

Страница 17: ...d screed with low thickness 6cm uf2 For traditional screed with thickness 6cm 29 Bp2 Floor covering choice Fl1 For tiles Fl2 For wood parquet floating or not 30 wir Pilot wire function for French Market application Use this option if your installation has the pilot wire installed in combination with an energy saver Yes Function activated No Function deactivated 31 min Minimal value of the setting ...

Страница 18: ...Page 18 HERZ Roomtemperature thermostat Installation Before the installation of the room temperature thermostat to the following steps have to be done 1 2 3 4 5 6 7 8 9 ...

Страница 19: ...mperature permanently to the chosen value depending on the adjusting knob ECO Decrease mode Select this mode to turn off the thermostat controlled area Therefore the gray plastic cover must be opened Decrease mode The set temperature is the temperature set by 2 Kelvin lower Comfort Mode The room temperature is regulated to the temperature which is set by the rotary knob The controller regulates ov...

Страница 20: ...ves Your product has been designed in conformity with the European Directives LVD 2006 95 EC EMC 2004 108 EC RoHS 2011 65 EU Product conformed to Classification UE 811 2013 und 2010 30 UE IV Mode When you modify the setting temperature or the mode the thermostat manages the receiver The LED flashes quickly in green for 2 seconds quick red flashes for low batteries indication When the batteries mus...

Страница 21: ...Page 21 HERZ Roomtemperature thermostat Installation Before the installation of the room temperature thermostat to the following steps have to be done 1 2 3 4 5 6 7 ...

Отзывы: