Testing and Calibration
Reset/Test button:
Once the unit is wired up properly, the unit can be put into one of five test modes. These modes are useful when setting
up and testing with the CAN bus controller.
Test 1
– Press the Reset/Test button on the board once and the unit will output 0% full scale weight.
Test 2
– Press the Reset/Test button on the board twice and the unit will output 25% full scale weight.
Test 3
– Press the Reset/Test button on the board three times and the unit will output 50% full scale weight.
Test 4
– Press the Reset/Test button on the board four times and the unit will output 75% full scale weight.
Test 5
– Press the Reset/Test button on the board five times and the unit will output 100% full scale weight.
Pressing the test button a sixth time will return the unit to normal operation. If the unit is left in test mode, it will
automatically return to normal operation after five minutes.
CAN Open Setup
Make sure the CAN protocol is set to CANopen.
|