INTRODUCTION

These instructions relate to the installation, basic connection and
setting-up of an HES91010 S

CENE

S

ET

Lighting Controller.

For operational instructions, please refer to the User Guide
(part no. I299GB) supplied separately.

INSTALLATION

Choosing a Suitable Location

The HES91010 is designed to be mounted vertically with the connection
points at the bottom; this is to ensure correct ventilation.

The chosen mounting surface must be flat and the location must meet the
following requirements:

·

A clearance of at least 100mm on all sides is recommended to allow
for adequate ventilation.

·

Sufficient clearance must be left below the unit to allow for the
connection of cables, conduits or trunking.

·

The ambient temperature must be within the range 0C to 35C and the
area must be adequately ventilated.

·

Humidity should be within the range of 0 to 90% (non-condensing).
DO NOT install this product in a damp location.

Fixing Method

Mounting is achieved by using the four ‘keyhole’ fixing holes on the side
flanges. The fixing screws (not supplied) must be chosen to suit the
following criteria:

·

Wall Construction

– suitable wall plugs must be used for masonry

construction and plasterboard partitions.

·

Screw Length

– must be sufficient to securely anchor the unit.

·

Screw Head

- round-head, pan-head or cheese-head screws must be

used. The head size should be small enough to just pass through the
large area at the centre of the fixing hole and large enough to clamp
the flange securely in the slotted portion of the hole.

1.

Mark and drill four holes to correspond with the centres of the
fixing holes (see Fig.1-1), and fit wall plugs as required. Note the
drop-down clearance of 12mm.

2.

Insert the screws, and screw them in until the distance between the
wall and the underside if the screw heads is a little more than the
depth of the flange.

3.

Align the centres of the flange fixing holes with the screws, then
allow
the slotted part of the holes to drop-down behind the screw heads.
If necessary, loosen the screws to ease this operation.

4.

Finally, tighten all four screws sufficiently to prevent the unit from
being lifted away.

211

230

181

370

251

93

63

(ALL DIMENSIONS IN mm.)

HES91010 SCENESET – LIGHTING CONTROLLER

Ø5.0

KEYHOLE SLOTS

(4 off) for securing the unit

Ø8.0

Drop Height

= 12mm

Fig.1-1: Overall dimensions & fixing holes positions.

Cable Access

There are various ‘knock-outs’ on the base of the unit which are suitable
for 15, 20, or 25mm conduit fixings (see Fig.1-2).

These are arranged such that the three left hand positions are used
exclusively for mains cables, whilst the remainder are used for the FELV
(Functional Extra-Low Voltage) control connections.

If required, control cables which are not in conduits can enter the unit via
the slot behind the knock-outs.

MAINS CABLES

LOW VOLTAGE CONTROL CABLES

Entry point for free cables

(not in conduit)

15

20

20

20

25

20

20

20

Fig.1-2: Cable entry knock-outs

Installation Instructions

S

CENE

S

ET

Lighting Controller

HES91010

Document Ref. EPD05113

(22/07/03)

ENGLISH

Part No. I259GB issue 6

Содержание SCENESET HES91010

Страница 1: ...hrough the large area at the centre of the fixing hole and large enough to clamp the flange securely in the slotted portion of the hole 1 Mark and drill four holes to correspond with the centres of the fixing holes see Fig 1 1 and fit wall plugs as required Note the drop down clearance of 12mm 2 Insert the screws and screw them in until the distance between the wall and the underside if the screw ...

Страница 2: ...and side and provides connection points to the various FELV Functional Extra Low Voltage data and control circuits see Fig 1 4 S COM external power data highway S COM star data highway S COM internal data highway S DIM data highways SCENESET watchdog relay contacts BREAKOUT module relay coil and contacts DIMMER level override input These allow the connection of various external control input or ou...

Страница 3: ...IM 1 or switch 8 DIM 2 to the ON position accordingly If the module is located at some point along the highway s set switches 7 or 8 to the OFF position S COM external This data highway is used to connect the following scene recall devices SCENECOMMANDERs SCENETIMER INPUT Module CHANNEL COMMANDER STAR DISTRIBUTION Unit also requires S COM star line Connection Details CAUTION Ensure that the SCENES...

Страница 4: ...fering different system capabilities Card Type Capacity Scenes Triggers Redirects Clusters HES90120 8K 40 10 10 2 HES90240 128K 600 150 150 15 HES91280 512K 1024 500 500 50 Choose the card type carefully to match current requirements and also allow for any anticipated future expansion Default Scene The SCENESOFT card can be programmed to perform one of two actions when the SCENESET controller is p...

Отзывы: