TB20, strain gauge weighing module | Edition 1 | 21.12.2018
61
9
Operation of the weighing module
9.1
Data transfer between the PLC and the weighing module
For the operation of the weighing module behind a TB20 bus coupler, a command must be carried out
once when starting up in order that the module is ready for operation (e.g. load
acknowledgment). The master writes data into the outputs and reads data from the inputs of the bus
coupler.
9.1.1
Setup of the control commands
Outputs: 7 bytes
7
6
5
4
3
2
1
0
OB 0 - 3
Sampling point value / offset (for example, 10000 transferred as 100.00 kg)
OB 4
Reserved
Reserved
Load
sampling
point 5
Load
sampling
point 4
Load
sampling
point 3
Load
sampling
point 2
Load
sampling
point 1
Load offset
OB 5
Acknowledg
ment for
"Control
command
has been
carried out"
Carry out
wire break
test
Output
sampling
point 5
Output
sampling
point 4
Output
sampling
point 3
Output
sampling
point 2
Output
sampling
point 1
Output
offset
OB 6
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
9.1.2
Setup of the response data
Inputs: 8 bytes
7
6
5
4
3
2
1
0
IB 0 - 3
Return value
Measurement value of the load cell or saved value (offset/sampling point)
(Transferred are, for example, 10000 as 100.00 kg or 2345 as 2,345 mV/V depending upon the issuing unit)
IB 4
1 = Ready
for
operation
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Value valid.
(=1)
IB 5
Control
command
was carried
out (= 1)
Reserved
ADC
overflow or
underflow
(=1)
Fault when
reading or
saving a
sampling
point/offset
(=1)
Reserved
Line break
(=1)
Bridge feed
voltage is
too large
(= 1)
Bridge feed
voltage is
too small
(=1)
IB 6
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
IB 7
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved