TB20, strain gauge weighing module | Edition 1 | 21.12.2018
32
4.3
Wiring the coupler
A power supply unit is integrated into the bus coupler. The power supply unit is responsible for
powering the peripheral modules connected to the coupler.
The power supply itself draws its power from the three-pin terminal on the front (24 V DC, GND,
AUX).
The 24 V connector is used to power two buses:
The power bus used to power the I/O components (24 VDC, GND, AUX)
The communications bus used to power the electronics in the peripheral modules
The AUX pin can be used to connect and use an additional voltage potential. Every peripheral module
has an AUX terminal on its front connector (the bottommost terminal, i.e., terminals 10 and 20).
The coupler and the modules are grounded via the shield contact to the DIN rail. The DIN rail must be
grounded. The surface of the DIN rail must be clean and conduct electricity well.