11.3 T2S
11.3.1 Removal
Use a small screw driver to release the latch keeping the T2S in position.
Pull the T2S out.
11.3.2 Inserting
Push the T2S firmly in place until the latch snaps in position.
11.4 Fan replacement
The FAN life is approx 60.000 (Sixty Thousand) hours. The inverter modules have fan runtime meters and fan failure alarm. Fan
failure can result from failing fan or driver circuit.
Let the module rest at least 5 minutes prior to initiating work.
The inverter front must be removed. Use a blunt tool to depress the latches on the module side fixing the front to the
module.
Remove the fan and unplug the supply cord.
Replace with new fan and connect supply cord
Replace front, make sure that the front latch properly.
Plug in
Check fan for operation
Access T2S and reset the fan run time alarm from within the action menu.
Once the FAN is replaced and module installed back in your system, You will need to clear the FAN alarm of the module.
This can be done through the T2S menu 3 Action then 2 inverter action then 13 Notify change FAN.
Refer to T2S manual for more details.