Gas fired igniter ZA0 / ZDA0
Installation and initial commissioning
- 42 -
Status: 11-2018
6.6
Checking the setting result
If correctly set, the following setting results should be in place
following initial commissioning:
Immediate ignition
Optically good flame pattern / flame signal 90
– 110 V DC, or
optimized ionisation flow > 10
A (test sockets in the front
panel of the igniter head in the standard version)
Flame length max. 600 mm at max. output of 120 kW and free
burn-out