Gas fired igniter ZA0 / ZDA0
Installation and initial commissioning
Status: 11-2018
- 35 -
Fig. 14: Terminal diagram IP 65, 7-core
Special version, IP 65
with 7-core control cable, sealed ionisation flame monitor
connection, type ZA0...
Core
Designation Meaning
PE
Protective earth conductor
1
N
Mains connection, ionisation flame
monitor
2
L
3
N
Spark transformer (primary)
4
L
5
+
Flame signal output 90
– 110 V DC
6
-
item 11
LED (flame present)
Fig. 15: Terminal diagram IP 65, 12-core
Special version, IP 65
with 12-core control cable, sealed ionisation flame monitor
connection, type ZDA0...
Core
Designation Meaning
PE
Protective earth conductor
1
N
Mains connection, ionisation flame
monitor
2
L
3
N
Spark transformer (primary)
4/5/6 *
SPDT contact (flame relay), max.
250 V AC, 1A, cos
φ 1 (ohmic), fusing
1A quick blowing on front plate
1)
8
L
Spark transformer (primary)
9
+
Flame signal output 90
– 110 V DC
10
-
item 11
LED (flame present)
1)
The special version with gold contacts is exclusively intended for connecting low power outputs (< 1 VA).