Heat & Glo • 6000CMOD-IPI, 8000CMOD-IPI • 2241-900 Rev. K • 4/14
Figure 7.4
Two Elbows
Note:
For corner installations: A 6 inch
(152 mm) section of straight pipe may
need to be attached to the appliance
before a 90º
elbow, to allow the vent
pipe to clear the top standoffs.
6000CMOD-IPI
V
1
Minimum
H
1
+ H
2
Maximum
Elbow only
Not allowed
6 in.
152 mm
2 ft.
610 mm
1 ft.
305 mm
4 ft.
1.2 m
1-1/2 ft.
457 mm
11 ft.
3.4 m
2 ft.
610 mm
17 ft.
5.2 m
2-1/2 ft.
762 mm
20 ft.
6.1 m
V
1
+ H
1
+ H
2
= 40 ft. (12.2 m) Maximum
H
1
+ H
2
= 20 ft. (6.1 m) Maximum
V
1
= 1 ft. (305 mm) Minimum
8
000CMOD-IPI
V
1
Minimum
H
1
+ H
2
Maximum
Elbow only
Not allowed
6 in.
152 mm
Not allowed
1 ft.
305 mm
2 ft.
610 mm
2 ft.
610 mm
4 ft.
1.2 m
3 ft.
914 mm
6 ft.
1.8 m
4 ft.
1.2 m
8 ft.
2.4 m
6 ft.
1.8 m
12 ft.
3.6 m
10 ft.
3.0
20 ft.
6.1 m
V
1
+ H
1
+ H
2
= 40 ft. (12.2 m) Maximum
H
1
+ H
2
= 20 ft. (6.0 m) Maximum
V
1
= 1 ft. (305 mm) Minimum
INSTALLED
HORIZONTALLY
H
1
H
2
V
1