SQ-Elite-MV & SQ-Elite-EXT Installation Manual 

 29

   followed by the minutes.  If hours are to be set to PM, scroll through the AM hours to reach the PM hours.

•   Remember that the battery is the backup for the Time.  If no power is supplied to the SQ-Elite-MV, the battery will die in three 

months and time clock values will be lost and will need to be reset.

dHw settIngs

•   A DHW call can be initiated by shorting the DHW input terminals, 

25 and 2

6.

•   In addition to raising the Target to lowest of 200ºF or the Maximum Target on a DHW call, the SQ-Elite-MV provides three levels 

of DHW Pump operation.  The first is when Primary/Secondary is selected as the DHW Piping from the Startup Menu.  (See 

DHW Piping on page 1

8

.)  This option will provide no DHW Priority.  Furthermore, a DHW call during the Summer or when the 

outdoor temperature is above the SEQ Outdoor Cutoff will energize both the DHW Pump and the System Pump relays.  Upon the 

termination of the DHW call, the DHW Pump relay will de-energize leaving the SEQ System relay energized for the Run-On delay.

•   The other two DHW options are available when Parallel is selected as the DHW Piping from the Startup Menu. (See DHW Piping 

on page 

1

8

.)  These two options will not allow the SEQ System relay to energize in Summer or outdoor cutoff situations.

•   In Winter, if the DHW Priority Timer was set to 

NO

, a DHW call will keep the SEQ System relay energized in addition to the 

DHW Pump relay.  Upon termination of the DHW call, the DHW Pump relay will de-energize leaving the SEQ System relay on.

•   In Winter, if the DHW Priority Timer was set to a time value, a DHW call will de-energize the SEQ System relay and energize 

the DHW Pump relay on a DHW call.  This will remain for the period of the DHW Priority Timer setting or until the DHW call 

terminates, whichever is sooner.  If the DHW call was still active after the DHW Priority Timer elapses, the SEQ System relay will 

energize for the remaining of the DHW call period.

dHw prIorIty tIMer

(aVaIlaBle wItH parallel dHw pIpIng)

Adjustable NO, 1 to 120 minutes 

Default: NO

Hold Button: 

MENU/<SEQ Settings>/<SEQ System Settings>/DHW Prior. Timer

•   The DHW Priority Timer provides the user with the capability of selecting the DHW

DHW PRIORITY TIMER

     30min

[            ]

BACK        SAVE

   Priority period.  If 

NO

 was selected, both DHW Pump and System relay will be energized on a DHW call whenever there is a 

DHW call during Winter.

•   In Summer or SEQ Outdoor Cutoff, a DHW call will energize only the DHW Pump relay leaving the System relay de-energized.

•   If the DHW Priority Timer was set to a value other than No, a DHW call in the Winter when the outdoor temperature is below the 

Outdoor Cutoff will cause the SEQ System relay to de-energize and the DHW Pump relay to energize for the period of the DHW 

Priority Timer or until the DHW call expertise, whichever happens sooner.  If the DHW call did not expire within the priority 

period, then the SEQ System relay will energize.

puMp and ValVe operatIon

•   The SQ-Elite-MV controls multiple relays each controlling a different type of equipment.  In addition to the control of the boilers, 

it can control, the SEQ System pump, MOV System pump, boiler pumps or valves, and the DHW Pump.  The operation of those 

relays depends on the Startup and SEQ and MOV Settings.

seQ and MoV run-on

Adjustable 0 to 60 minutes 

Default: 2 minutes

Hold Button: 

MENU/<SEQ Settings>/<System Settings>/Run-On

•   The Run-On applies to all pumps and valves.  It is the time a pump or valve will run after 

the output boiler relays has de-energized.  After the pump or valve goes through the Run-On 

period, its relay de-energizes.  For pumps and valves the Run-On is used to dissipate the 

excess energy from the heating system into the building.

------- RUN-ON -------

     2min

[

          ]

BACK        SAVE

•   A boiler pump or valve will go through the Run-On when all the stages on that boiler has turned off.  This will take place for all 

boiler pumps and valves except for the lead boiler valve.

•   The Run-On will take place for the lead boiler valve and System relays whenever the season is changed to Summer, the outdoor 

temperature rises above the SEQ Outdoor Cutoff, or the Shutdown or SEQ Tstat is activated.

•   The Run-On time should be set based on the size and type of the equipment.  A boiler with high water content and high horsepower 

will need a longer Run-On than a boiler with the same horsepower but has less water content.

seQ and MoV puMp eXercIse

Adjustable Off, On 

Default: Off

Hold Button: 

MENU/<SEQ Settings>/<System Settings>/Pump Exercise

•   The SQ-Elite-MV provides an option to exercise pumps for 10 seconds when not used for 

seven day to reduce pump impeller locking after off-season.

--- PUMP EXERCISE --

 

Off

 On

BACK        SAVE

Содержание SQ-Elite-EXt

Страница 1: ...CONTROL MOV CLOSE INPUT RATINGS 120VAC 60Hz 12VA MAX Use Copper Conductors Only CAUTION Risk of Electric Shock PWR L N 1 2 SENSORS MUST BE GOLD SERIES MOV SYS 3 MOV CLOSE 5 Stage A 7 Stage B 9 Stage C...

Страница 2: ...g settings 22 Program Change Settings 22 Season 22 seQ and MoV reset ratio settings 22 SEQ and MOV Reset Ratio 22 SEQ and MOV Customized Reset Ratio 22 SEQ and MOV Target Offset 23 SEQ and MOV Outdoor...

Страница 3: ...2A 120VAC MAXIMUM 15A TOTAL FOR ALL CIRCUITS 23 24 MOV OPEN DO NOT APPLY ANY VOLTAGE TO INPUT TERMINALS MOV OPEN MOV SYS SEQ Temp ENCLOSED ENERGY MANAGEMENT EQUIPMENT LISTED 99RA C US Press any button...

Страница 4: ...s to quickly make changes to any system setting without having to learn any specialized codes or keyboard commands Two separate menus has been provided One for the installer having all the functions W...

Страница 5: ...this means the temperature has fallen 20 from the starting point of 70 F Therefore the heating water temperature will increase 20 to 120 F Each building has different heat loss characteristics A very...

Страница 6: ...eset or by maintaining an adjustable Set Point The Outdoor Reset option uses an Outdoor Sensor supplied with the control and achieves better fuel savings in addition to better comfort Using an optiona...

Страница 7: ...inals This switch is enclosed with the enclosure wiring cover for security Wiring terminals are of the plug in type to ease installation and removal The Enclosure Base contains the holes to mount and...

Страница 8: ...or Shield alert If any of the System Sensors cannot sense the correct system water temperature the SQ Elite MV will not provide comfortable heat levels outdoor sensor InstallatIon Only use the Heat Ti...

Страница 9: ...temperature Whether in Set Point or Outdoor Reset modes the outdoor sensor can be used as an Outdoor Cutoff The SQ Elite MV will disable all Boilers and close the motorized valve when the outdoor tem...

Страница 10: ...V will sequence the stages to achieve the desired SEQ Set Point However when the terminals are opened all stages will de energize The Tstat signal must be a dry contact only No voltage can be placed a...

Страница 11: ...DHW during Summer or when SEQ Tstat input is opened DHW PUMP 13 Stage E 15 Stage F 17 12 14 16 18 19 SEQ SYS SEQ System Pump L N wIrIng tHe MoV systeM output terMInals 19 20 Connect the MOV pump Motor...

Страница 12: ...igher stage of the same boiler must be connected to Stage B The boiler valve or pump must be connected to Stage C PWR L N 1 2 3 5 Stage A 7 Stage B 9 Stage C 11 13 Stage E 15 Stage F Stage D 6 8 10 12...

Страница 13: ...Two Extension Panels and 4 20mA EMS Interface using RS485 SQ Elite MV SQ Elite MV SEQUENCING CONTROL INPUT RATINGS 115VAC 60Hz 12VA MAX Use Copper Conductors Only CAUTION Risk of Electric Shock Stage...

Страница 14: ...Stages On Stages Off BACK SAVE ARE YOU SURE No Yes BACK SAVE eMs set poInt MAINTENANCE Unit F Present Time12 30P Valve Sensor Trim Histories Configuration BACK SELECT SENSOR TRIM SEQ Trim 0 F Outdoor...

Страница 15: ...00 SYS 12 1 00 OD 4 00 SYS BACK SAVE SEQ OUTDOOR RESET Reset Ratio 7 Target Offset 0 F Outdoor Cutoff 70 F Min Target 80 F Max Target 240 F BACK SELECT TARGET OFFSET 0 F BACK SAVE MIN TARGET 80 F BACK...

Страница 16: ...ings Setback Schedule DHW Prior Timer No Run On 2m Pump Exercise Off BACK SELECT STAGE SETTINGS Reaction Time 1min Purge Delay 0 0min Min Runtime 2min Standby Delay10min Last Stge Hold 5 F Throttle 2...

Страница 17: ...1 50 OD 1 00 SYS 6 1 25 OD 1 00 SYS 7 1 00 OD 1 00 SYS 8 1 00 OD 1 25 SYS 9 1 00 OD 1 50 SYS 10 1 00 OD 2 00 SYS 11 1 00 OD 3 00 SYS 12 1 00 OD 4 00 SYS BACK SAVE MOV OUTDOOR RESET Reset Ratio 7 Targe...

Страница 18: ...y of displaying temperature information and settings in either F Fahrenheit or C Celsius Select the display unit that is best suited for your application DISPLAY UNIT F C BACK SAVE settIng tHe 4Ma and...

Страница 19: ...ized If SEQ Prove is selected make sure to connect those terminals to either a flow switch that checks the SEQ System pump operation or a combustion air damper end switch Otherwise install a jumper on...

Страница 20: ...he following are the settings that directly affects this modes operation Reaction Time Hold Button MENU SEQ Settings System Settings Stage Settings Reaction Time Purge Delay Hold Button MENU SEQ Setti...

Страница 21: ...et to the MOV Maximum Target set poInt Mode If Valve Close is selected the SQ Elite MV will energize the MOV Close relay when the SEQ System sensor reads Short or Open If Valve Open is selected the SQ...

Страница 22: ...g Outdoor Rst Reset Ratio SEQ Hold Button MENU MOV Setting Outdoor Rst Reset Ratio MOV The Reset Ratio determines how the System water temperature will vary with outside temperature changes With any o...

Страница 23: ...ding Operation Concept on page 5 The Minimum and Maximum Target will take precedence over the Offset That is if the Max Target was set to 180 F and the Offset was set to 20 F If the set point was 170...

Страница 24: ...EQ System temperature around the SEQ Set point If the EMS Mode was Enabled the Set Point will be set by the EMS BMS system and will be available as a read only The range of Set Point in the EMS is set...

Страница 25: ...URGE DELAY 0 0min BACK SAVE The Purge Delay helps prevent short cycling of a newly activated boilers Once the lowest boiler stage is activated it MUST run through the entire Purge Delay period The min...

Страница 26: ...ng range as a differential The last stage to be turned off will be allowed to exceed the Set Point by a full Throttle before it is turned off This helps prevent the last stage from short cycling when...

Страница 27: ...he automatic rotation is recommended for most applications The current Lead Boiler is shown in brackets on the main display Only boilers which are set to Auto Mode can be Lead Therefore not all the bo...

Страница 28: ...ost will take place after the Setback is deactivated If 0 F Was selected no boost will take place seQ and MoV Boost perIod Adjustable 0 to 120 minutes Default 0 minutes Hold Button MENU SEQ Settings S...

Страница 29: ...30min BACK SAVE Priority period If NO was selected both DHW Pump and System relay will be energized on a DHW call whenever there is a DHW call during Winter In Summer or SEQ Outdoor Cutoff a DHW call...

Страница 30: ...that time and read the upper left temperature SEQ 120 F 10 00AM BACK NEXT The first screen will be the SEQ System Temperature History By clicking on the Next button you ll be able to view the Outdoor...

Страница 31: ...the SEQ Set Point to the indicated temperature DHW increases calculated temperature to the lower of 200 F or Max Water Holding Return at 110 F The Return sensor is reading less than the Minimum Retur...

Страница 32: ...o active boilers Any output without an active boiler must be set to Off The following list describes the MODE options BOILER AB MODE Auto Standby Off On BACK SAVE Auto The SQ Elite MV will control the...

Страница 33: ...st and Boost Period values Reduce the Boost amount or Boost Period setting See Boost on page 28 Boiler Mode Settings The SQ Elite MV will only sequence boilers their mode is set to Auto or Standby Che...

Страница 34: ...set See MOV Offset on page 23 Setback and Day Night Schedule If reduced heat occurs during Night hours reduce the MOV Setback setting See MOV Setback on page 28 If the building takes a long time to re...

Страница 35: ...r continuity across terminals 23 and 24 Otherwise the SQ Elite MV may be damaged Boilers are short cycling Minimum Runtime Increase the Minimum Runtime only if all boilers tend to short cycle Last Sta...

Страница 36: ...Temp Outdoor Temp MOV CLOSE SEQ SYS DHW PUMP MOV OPEN SEQ SYS SENSORS MUST BE GOLD SERIES DO NOT APPLY ANY VOLTAGE TO INPUT TERMINALS Use Copper Conductors Only CAUTION Risk of Electric Shock PROGRAM...

Страница 37: ...37 38 SEQ PROVE MOV TSTAT 23 24 MOV OPEN SEQ Temp Outdoor Temp MOV CLOSE SEQ SYS DHW PUMP MOV OPEN SEQ SYS SENSORS MUST BE GOLD SERIES DO NOT APPLY ANY VOLTAGE TO INPUT TERMINALS Use Copper Conductors...

Страница 38: ...ROVE MOV TSTAT 23 24 MOV OPEN SEQ Temp Outdoor Temp MOV CLOSE SEQ SYS DHW PUMP MOV OPEN SEQ SYS SENSORS MUST BE GOLD SERIES DO NOT APPLY ANY VOLTAGE TO INPUT TERMINALS Use Copper Conductors Only CAUTI...

Страница 39: ...age C 11 13 Stage E 15 Stage F 17 Stage D 6 8 10 12 14 16 18 RS485 4 SEQ SYS 19 DHW PUMP 21 27 29 31 MOV Temp 33 SHUTDOWN TSTAT SETBACK 35 Return Temp 20 22 28 30 32 34 36 25 26 DHW 37 38 SEQ PROVE MO...

Страница 40: ...00 SYS 3 3 00 OD 1 00 SYS 4 2 00 OD 1 00 SYS 5 1 50 OD 1 00 SYS 6 1 25 OD 1 00 SYS 7 1 00 OD 1 00 SYS 8 1 00 OD 1 25 SYS 9 1 00 OD 1 50 SYS 10 1 00 OD 2 00 SYS 11 1 00 OD 3 00 SYS 12 1 00 OD 4 00 SYS...

Страница 41: ...eeded as well as preserve the battery life seQ and MoV reset ratIo settIngs Each of the boiler loop SEQ and motorized valve loop MOV has their own reset ratio settings that can be configured independe...

Страница 42: ...Point temperature was 130 F and the Offset was changed from 0 to 10 an increase of 10 then the Set Point temperature would increase to 140 F TARGET OFFSET 0 F BACK SAVE The Offset setting does not ch...

Страница 43: ...ar on the main display indicating this condition Setback to 160 F For example if the calculated temperature is 180 F and the Setback is 20 F then when in Setback the SQ Elite MV will hold a Set Point...

Страница 44: ...4 20mA EMS Interface optional Reset Ratio Range Outdoor Reset Only 1 4 to 8 1 Outdoor System Water and Custom Reset Ratio Offset Adjustment Outdoor Reset Only minus 40 F 22 C to plus 40 F 22 C Minimum...

Отзывы: