Make sure you Have tHe rIgHt control
If you need the Mini-MOD to do additional tasks that either are not listed or do not know how to configure them, contact Heat-Timer
Corp. Sales Department either by Phone (973)575-4004, Fax (973) 575-4052, or by E-mail [email protected].
InItIal setup
Setting an Initial Program will ease the configuration of the Mini-MOD and will give the opportunity to utilize many of the energy saving
features and give more comfortable heat when needed.
The program should consist of the following:
• Selecting the features that your system can utilize,
• Installation: Install the Control, switches and sensors,
• Setting the System Startup,
• Setting the System Settings,
• Setting the Stages
• Adjusting Reset Ratio and Water Offset (In Reset Mode Only)
selectIng tHe systeM features
The Mini-MOD has been designed with Hydronic building heating as the primary purpose. With this in mind, many of the Mini-MOD
features can be utilized to ease, enhance and improve your system performance. Some of these features are listed in this section.
outdoor reset or set poInt
• The Mini-MOD can control the System Temperature either by adjusting the calculated temperature according to the Outdoor Temperature
(Outdoor Reset) or by maintaining an adjustable fixed Set Point. The earlier relies on an Outdoor Sensor (supplied with the control)
and achieves better fuel savings in addition to better comfort.
nuMber of stages
• The Mini-MOD can be configured to control up to 4 modulating boilers. It can control up to 16 boiler stages using a maximum of two
Mini-MOD Extension Panels
ModulatIon Mode
• The Mini-MOD can stage boilers using one of two methods. Normal Modulation Mode, allows it to increase the modulation of the
lead boiler. When the lead boiler reaches its modulation start point adjustment and does not satisfy the load, the Mini-MOD will start
the next boiler and so on. This mode targets boilers that can run more efficient at higher modulation rates.
• The Parallel Modulation Mode can modulate several boilers together as one large boiler. This mode is useful for boilers that are
more efficient at lower firing points.
ModulatIng sIgnal
• The Mini-MOD is designed to accurately control the output from 0 to 100% of modulation for each of these different types of motors.
One Mini-MOD can even control a variety of the above different modulation motors.
autoMatIc rotatIon aMong boIlers
• Rotating the first burner to be activated on a call for output promotes even wear on all burners. The Mini-MOD has three modes of
rotation: Manual, Last-ON, or Time automatically rotating every selected time period from every hour to every 60 days.
standby boIler
• Any boiler can be configured as a Standby boiler. It withholds a specific boiler from being included in the Lead Rotation. However,
the Standby boiler will be fired only as a backup when all other stages combined cannot satisfy the demand and after an adjustable
delay period.