059705–00 REV. B
|
19
08
SPECIFICATIONS
GENESIS HEAT-TIMER
®
CONTROL
Voltage Input
120VAC, 60 Hz
Maximum Input Rating
30VA
Dimensions (W x H x D)
11” x 9” x 3¾” (279.4mm x 228.6mm x 95.25mm)
Weight
2.5Lbs (1.13kg)
Output Relays
System/Pump I Boiler I Valve I Modem
Output Relays Rating
120VAC, 3 Amp Resistive
1 Amp Pilot Duty
120VAC, 1 Amp Resistive (Modem)
Inputs
System Temperature
Outdoor Temperature
DHW Call
(3) Optional Temp or Switch Inputs
User Interface
Digital Display
Display Units: Temperature (°F and °C)
Status Indicators (3 LEDs)
Variable-Function Buttons (4)
Modulating Output Types
4–20mA, 0–5V, 0–10V, 1–5V, 2–10V