ETV Platinum Plus Control Module Output Status LEDs
The ETV Platinum Plus has
three output status LEDs:
Display and Variable-Function Buttons
The ETV Platinum Plus display shows the system sensor
temperature and operation messages. By default, the
display shows the current Setpoint, Alarm Limit(if
applicable), or the Modulation Output percentage. See
“Display Icons and Messages” on page
36 for more information.
The area above the variable-function buttons displays the
current function for each button. This area may not be
displayed if button activity is stopped for 30 seconds in
the ETV + TMC mode.
The display button functions vary based on the current screen displayed, as described in the following table:
LED
Description
Actuator Signal
Indicates the change in the mixing valve opening. Any time the ETV Platinum Plus changes
the valve opening, the LED will turn on for approximately one second. If the LED remains
lit, the control is sending the Actuator a “fully open” or “fully close” signal.
No Flow
Indicates no flow exists when lit.
TMC Lockout
Indicates the control is in lockout mode when lit. System temperature rises above the Alarm
Limit for the Trigger Delay period, or a sensor has been disconnected. See
“Alarm Messages” on page
35
.
After the alarm condition has been corrected, the ETV Platinum Plus must be manually
reset to resume normal operation.
Screen
Button
Left
▲
▼
Right
Default
Has no function
Has no function
MENU
Enters the menu mode.
In Lockout
LOCKOUT
Enters the Lockout Reset
Menu.
Lockout Reset
BACK
Goes back one menu step.
RESET
Ends current alarm.
Menu
Scrolls through the menu.
SELECT
Selects current menu item.
Setting
Changes the current setting value.
SAVE
Saves current setting.
Configuration
NEXT
or
EXIT
Jumps to next view or exits.
Содержание ETV Platinum Plus
Страница 9: ...ETV Platinum Plus Stainless Steel Valve Dimensional Specifications 9 059305 00 Rev D Heat Timer Corp...
Страница 31: ...Piping Diagrams 31 059305 00 Rev D Heat Timer Corp Figure 14B Two Mixing Valves and a TMC Safety Valve...
Страница 54: ...059305 00 Rev D Heat Timer Corp Notes 54 ETV Platinum Plus Installation and Operation Manual...
Страница 55: ...059305 00 Rev D Heat Timer Corp Notes ETV Platinum Plus Installation and Operation Manual 55...