DHW Energy Saver Installation and Configuration Manual  

3

HT# 059106-00C

Overview

The DHW (Domestic Hot Water) Energy Saver connects to a Heat-Timer RINet Platinum series control (all MPC, 

MPCQ, HWR, HWRQ, SRC RINet Platinum controls with software version 7.05 or higher) to operate a boiler or direct/

indirect water heater and a DHW circulating pump based on two set points.  One set point is for the boiler and the other 

is for the pump.  Two sensors connected to the Platinum RINet (Internet communication capable control) are used.  

Aux Temp 0 sensor measures the domestic hot boiler supply temperature.  Aux Temp 1 sensor measures the domestic 

recirculating line return temperature.

All the DHW Energy Saver settings can be viewed and adjusted through the Platinum control menus or the Platinum  

control pages on ICMS website (http://www.htcontrols.com).  Each of the supply and return temperatures have a set point 

and a peak demand and light load condition differentials.  This offers better operation and savings than one differential.  

As the goal is to reduce boiler/water heater and pump operation during light periods.  That can be achieved by having 

slightly longer boiler/water heater run periods and longer off periods using a larger differential.  When the supply 

temperature drops below the Supply Set Point and differential, the Control will energize the boiler output.  The boiler 

output will remain energized until the supply temperature reaches the Supply Set Point.  When the return temperature 

drops below the Return Set Point less the differential, the Control will energize the circulating pump output.  The pump 

output will remain energized until the return temperature reaches the Return Set Point.

 

WARNING

•   Make sure Recirculating Pump control does not adversely affect other equipment.  I.e. tempering valve.

•   Make sure the boiler/water heater can operate properly at the lowest desired differential adjustment.

The Platinum control has a separate DHW Energy Saver weekly Day/Night schedule that can be set using the Internet 

ICMS web site or through the Platinum control menu.  It offers 4 peak and 4 light load periods for each day of the week.  

When in the peak period, the Platinum control will use the Peak Differential setting.  When in the light usage period, the 

Platinum control will use the Light Differential setting.  The Light Differential must be greater than the Peak Differential 

to provide longer boiler or pump runtime and longer off periods.

DHW Energy Saver

Boiler

Pump

6

7

8

9

COM

3

4

5

A   GND   B

16VAC

1

2

~      ~

Typical Wiring for Platinum

Serial Panel RS485 Plug

16 VAC

(transformer

Provided)

Communication to

Heat-Timer 

Platinum Control

DHW boiler and

DHW circulating

pump output relays

Содержание DHW Energy Saver

Страница 1: ...y an operating control it should never be used as a primary limit or safety control All equipment must have its own certified limit and safety controls required by local codes The installer must verif...

Страница 2: ...re Sensor 5 Return Temperature Sensor 5 PLATINUM CONTROL MENU SETTINGS 6 ICMS WEB MENU SETTINGS 6 Using the Supply or Return Sensor 7 Supply or Return Set Point 7 Supply or Return Peak and Light Diffe...

Страница 3: ...the supply temperature drops below the Supply Set Point and differential the Control will energize the boiler output The boiler output will remain energized until the supply temperature reaches the Su...

Страница 4: ...ol Connect the transformer outputs to the DHW Energy Saver s left most terminals Power polarity is not observed WARNING DO NOT share the DHW Energy Saver transformer with other devices This may cause...

Страница 5: ...anual operation of the pump DHW Energy Saver Boiler Pump 6 7 8 9 COM 3 4 5 A GND B 16VAC 1 2 DHW Pump L N Bypass Switch Optional Temperature Sensor Wiring Only use a Standard Brass Tube sensor provide...

Страница 6: ...HW SETTINGS Supply Settings Return Settings Demand Schedule Copy Schedule DHW Settings DHW SUPPLY SETTINGS Use Sensor Yes Setpoint 140 F Peak Diff 20 F Light Diff 40 F DHW RETURN SETTINGS Use Sensor Y...

Страница 7: ...relay will de energize The circulating pump relay will energize whenever the return temperature drops below this set point less the differential See next setting DHW SUPPLY SETPOINT 140 F DHW RETURN S...

Страница 8: ...on the ICMS web site Select Alarm Delivery Setup and then Add Delivery for the Sensor Fault WARNING The boiler water heater must have its operating and limit controls installed and wired in a way so...

Страница 9: ...X CLOCK T T C O R P O R A T I O N R 2 3 4 5 5A 6 7 8 9 11 12 13 14 15 16 17 OUTPUT RATINGS 120VAC 6A RESISTIVE 1A PILOT DUTY 15A TOTAL FOR ALL CIRCUITS INPUT RATINGS 115VAC 60Hz 30VA MAX USE COPPER WI...

Страница 10: ...ESS TO SELECT BACK MON 12 28 04 10 43Am ADJUST A1 A2 A3 A4 A5 A6 A7 A8 A9 A10 A11 A12 AUX TEMP 2 DO NOT APPLY ANY VOLTAGE TO SENSOR TERMINALS A13 A14 A15 A16 A17 A18 NETWORK PROVE SHUTDOWN SYSTEM TEMP...

Страница 11: ...OUTPUT RATINGS 120VAC 6A RESISTIVE 1A PILOT DUTY 15A TOTAL FOR ALL CIRCUITS INPUT RATINGS 115VAC 60Hz 30VA MAX USE COPPER WIRE CLASS 1 WIRE ONLY ENCLOSED ENERGY MANAGEMENT EQUIPMENT 99RA PREV DEL OUT...

Страница 12: ...ltage Input 16 VAC transformer provided minimum 10VA Output Relays 2 N O SPST Each a maximum HP pump or 6 Amp resistive load at 120 VAC 60 Hz Outputs DHW boiler water heater and DHW pump Communication...

Отзывы: