2-Way Motorized Valve with Feedback installation Manual

HT# 059301-00 

A

actuator Manual Operation

The actuator Red Crank is used to operate the valve manually in periods of 
no power or when installing or servicing the equipment.

•   First, make sure that the Power Switch is turned Off prior to operating the 

actuator manually.

•   Pull the Crank Handle out and press it down to move the Actuator Shaft.
•   Turn the Crank Handle clockwise to move the Actuator Shaft down (Close 

Valve).

•   Turn the Crank Handle counter-clockwise to move the Actuator Shaft up 

(Open Valve).

1) turn power
    switch Off

2)  pull crank Handle Out

3)  press Down and turn

Wiring

•   The Heat-Timer Motorized Valve can be used with virtually any floating motor controller.  However, it is designed to 

work with Heat-Timer controls.

•   The actuator/motor uses a floating type signal (R. W. B.).
•   The actuator must be powered using the provided 24 VAC transformer.  A single transformer can only power a 

single actuator.  The transformer is supplied with every complete valve package.

•   Remove the Red Actuator cover to reveal the wiring terminals.
•   After finalizing the wiring, reinstall the actuator Red cover.
•   Auto Calibrate the SRC Platinum control to the motorized valve.  See SRC Platinum Manual.

Wiring the actuator power

•   Wire one of the 24VAC transformer outputs to the Actuator (1) Common terminal.
•   Wire the second 24VAC transformer output to the SRC Platinum (15) Common output terminal.
•   Connect the SRC Platinum (14) output terminal to the Actuator (2) Close terminal.
•   Connect the SRC Platinum (16) output terminal to the Actuator (3) Open terminal.

Wiring the actuator Feedback

•   Connect the SRC Platinum (A4) input terminal to the Actuator (10) terminal.
•   Connect the SRC Platinum (A5) input terminal to the Actuator (9) terminal.
•   Connect the SRC Platinum (A6) input terminal to the Actuator (8) terminal.

Содержание 928051-50-VM

Страница 1: ...y control All equipment must have its own certified limit and safety controls required by local codes The installer must verify proper operation and correct any safety problems prior to the installati...

Страница 2: ...ped per the following packing lists Valve package actuator package Valve Bushing Locknut Actuator Actuator Brass Bracket with two hex screws and two nuts Hex Wrench 5 24 VAC Transformer Stem Nut Stem...

Страница 3: ...the valve Remove the Actuator Brass Brackets This should release the Stem Attachment Thread the Stem Attachment to the Valve Stem Make sure that it is tightened against the Stem Nut Mount the Actuato...

Страница 4: ...oating type signal R W B The actuator must be powered using the provided 24 VAC transformer A single transformer can only power a single actuator The transformer is supplied with every complete valve...

Страница 5: ...SENSORS INPUTS ROUTE SENSOR AND AUXILIARY WIRES THROUGH THIS KNOCKOUT ONLY SYS AUX CLOCK OPTION 1 T T Cycle On 5 60m Val 45 Day OD 31 o F SYS 148 o F OUTPUT T T C O R P O R A T I O N R 2 3 4 5 9 10 12...

Страница 6: ...Bronze 88 32 to 300 4 928054 00 VM 170 13 6 22 Flanged Iron Bronze 135 32 to 300 5 928055 00 VM 280 15 5 23 Flanged Iron Bronze 150 32 to 300 6 928056 00 VM 360 17 6 23 Flanged Iron Bronze 191 32 to...

Страница 7: ...ted to the heating system boilers or electrical power system that is required for proper operation of any controls or other equipment installed by Heat timer corporation or any contractor third party...

Страница 8: ...actuator for manual operation Mounting Vertical above center line of valve Feedback Signal 1K ohm Terminals 8 9 10 2 Way Valve Specifications Body 1 2 Valves ANSI B16 15 Bronze 250lb Threaded NPT 2 1...

Отзывы: