Heat IQ AS10/15V Скачать руководство пользователя страница 1

Is this HP providing DHW  via a cylinder as well as  a heating output

Yes hot water is included

No the system is heating only

Access  codes 

for service  

level settings is 

9957  

Details to enter passcode 
can be found in the 
manual  Pg23

Exit the service parameters  and return to the main screen  

Now 

set a demand for heat  from at least one of the attached heating  system controls

After a couple of minutes the actuators on the manifold  for the respective control will  be open, 

After a further 2 or 3 minute time delay, the under floor wiring centre should call for the HP to run.

The HP   Circulation pump will run and the icon will appear, followed by the fan and then the compressor . 

In 

service parameters -

set 

SF05 

to  

"Yes ".                          

set

SF13  

to   

"Keyboard".

Set 

SF14 

to

"Remote"

In 

service parameters -

set 

SF05

to  

"No ". 

set  

SF14  

to  

"Remote"

At this point the HP  may go into alarm (AL17) Inadequate flow.

A common issue caused by  air in the system being trapped in the 

HPs plate heat exchanger.  In 'Manufacturer' settings  you can increase  the Pump minimum Speed' (EV06 - Default 30%)  by 
increments of 5% until adequate flow is achieved and no flow alarm is triggered.  -

Do not raise this more than you have to...

If you have to raise more than 5%  you must return to drop it  back again  after a period of 2/3 days running 

Now set User setting 

ST02 (Heating Output)

to between 

40-45 °

Heating output  - or as prescribed in the 

design provided for the under floor system attached .

After around 15 minutes running the HP should ideally have differential in temperature  between  4 and 6 degrees  

between the flow and return  temperature readings. 

Now make sure all the system zone controls are operating and opening the correct floor loops  

-

With all the loops 

calling, set the flow rates  to the given values provided in the system design  

-

Where the design gave a flow rate 

under 0.75 L  raise it to 0.75 as a minimum to prevent  blockages the flow meter apertures.

The system should  be left operational for  1 or 2 days  with an Auto fill valve  set at 1.2 bar left open in the filling loop  to 

replenish any latent air removed  by the systems auto air relief valves, after which the installer should disconnect the 

auto filling device 

.

For installs in potentially  Sub Zero  environments  it is the installers responsibility to  determine if Glycol  should be added for 
frost protection . We do not  make any allowance for this  even  in an instance where we provided system design . Likewise  any 
requirements for environmental  protection of HPs  in coastal or sulphurous  environments is the responsibility of the installing 
contractor. 

Refer to the manual for more information

It is Important to note, this Quick start guide is to assist you. It may not cover every requirement of a given installation. 
As the Installer it is your obligation to read  the installation manual & understand the appliance principals of operation. 
We accept no liability under warranty where failure is the result of  incorrect installation or  incorrect commissioning .  

Please ensure you complete and return the Commissioning/warranty registration  sheet              

Without it the warranty on this appliance is limited 

Heat 

IQ AS10/15V 

Inerter HPs   

Quick Start Guide   

Read and use this document in conjunction with the full appliance manual 

Before you start - Ensure the HP is secured to its base & level on both planes.  The heating system has been flushed and that 
the correct inhibitor has been added.  System pressure is set at 1.2 to 1.4 bar.  and all electrical connections  are correct.  

Now you can proceed to commission following the instructions below

This HP has a Compressor oil pre heater, Power must be on with no call for heat 
or hot water for a 

minimum Two hours

before starting this appliance 

See over for further information re setting up DHW 

Отзывы: