Heat & Glo  • SL-5F, SL-7F Installation Manual  •  2499-980 Rev. L  •  10/19 

Models:

Installation Manual

Installation and Appliance Setup

INSTALLER:  Leave this manual with party responsible for use and operation.

OWNER:  Retain this manual for future reference.

NOTICE: DO NOT

 discard this manual!

In the Commonwealth of Massachusetts installation must be 

performed by a licensed plumber or gas fitter.

See Table of Contents for location of additional Commonwealth 

of Massachusetts requirements.

This appliance may be installed as an OEM 

installation in manufactured home (USA 

only) or mobile home and must be installed 

in accordance with the manufacturer’s 

instructions and the 

Manufactured Home 

Construction and Safety Standard,

 

Title 24 

CFR, Part 3280 

in the United States, or the 

Standard for Installation in Mobile Homes, 

CAN/CSA Z240 MH Series,

 in Canada.

This appliance is only for use with the type(s) 

of  gas  indicated  on  the  rating  plate.  This 

appliance is not convertible for use with other 

gases, unless a certified kit is used.

DANGER

HOT GLASS 

WILL 

CAUSE BURNS.

DO NOT TOUCH 

GLASS 

UNTIL COOLED.

NEVER 

ALLOW CHILDREN

 TO TOUCH GLASS

.

A  barrier  designed  to  reduce  the  risk  of 

burns from the hot viewing glass is provided 

with this appliance and shall be installed for 

the  protection  of  children  and  other  at-risk 

individuals.

• 

DO NOT

 store or use gasoline or other flam

-

mable vapors and liquids in the vicinity of this 

or any other appliance.

•  What to do if you smell gas   

DO NOT

 try to light any appliance.

DO NOT

 touch any electrical switch. 

DO 

NOT

 use any phone in your building.

-  Leave the building immediately.

-  Immediately call your gas supplier from 

a neighbor’s phone. Follow the gas sup

-

plier’s instructions.

-  If you cannot reach your gas supplier, call 

the fire department.

•  Installation and service must be performed 

by a qualified installer, service agency, or the 

gas supplier.

WARNING: 

FIRE OR EXPLOSION HAZARD

Failure to follow safety warnings exactly 

could result in serious injury, death, or 

property damage. 

SL-5F

SL-7F

Содержание SL-5F

Страница 1: ...d on the rating plate This appliance is not convertible for use with other gases unless a certified kit is used DANGER HOT GLASS WILL CAUSE BURNS DO NOT TOUCH GLASS UNTIL COOLED NEVER ALLOW CHILDREN T...

Страница 2: ...t Information A Vent Termination Minimum Clearances 12 B Vent Terminal Clearances 13 C Approved Pipe 14 D Use of Elbows 15 E Measuring Standards 16 F Use of Flex Vent 17 G Vent Diagrams 17 5 Vent Clea...

Страница 3: ...moved inside outside of appliance ___________________________ Refractories logs media and embers installed correctly ___________________________ Glass assembly installed and secured __________________...

Страница 4: ...ed with ground fault circuit interrupter protection in compliance with the applicable electrical codes when it is installed in locations such as in bathrooms or near sinks NOT INTENDED FOR USE AS A PR...

Страница 5: ...fu eled heating appliance or equipment The sign shall read in print size no less than one half 1 2 in in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OB STRUCTIONS Inspection The state or local gas...

Страница 6: ...or remote control are desired Improper installation adjustment alteration service or maintenance can cause injury or property damage For assistance or additional information consult a qualified servic...

Страница 7: ...ers Hammer Phillips screwdriver Manometer Gloves Framing square Voltmeter Electric drill and bits 1 4 in Plumb line Safety glasses Level Reciprocating saw Flat blade screwdriver Non corrosive leak che...

Страница 8: ...4 41 1041 B 31 1 8 791 36 1 8 918 C 27 3 16 691 32 1 16 814 D 18 1 16 459 21 1 2 546 E 34 1 16 865 37 5 8 956 F 3 9 16 90 3 9 16 90 G 6 7 8 175 6 7 8 175 H 23 3 8 594 26 7 8 683 I 34 3 8 873 37 7 8 96...

Страница 9: ...in 30 5 16 27 1 4 29 1 2 25 7 8 28 3 4 2 3 16 1 1 2 mm 770 692 749 657 730 56 38 SL 7F in 35 13 16 31 1 8 34 3 8 29 5 8 32 1 2 2 1 8 1 5 16 mm 910 791 873 752 826 54 33 FIRESCREEN DECORATIVE FRONTS Fa...

Страница 10: ...n to scale Actual installation may vary due to individual design preference Figure 3 3 Appliance Locations K C A L F I B G E D J J G A F C A H M N Refer to Section 10 B for mantel and wall projection...

Страница 11: ...nt accidental contact The chase must be properly blocked to prevent blown insulation or other combustibles from entering and making contact with fireplace or chimney Failure to maintain airspace may c...

Страница 12: ...Fuel Oil Termination Cap B Gas Termination Cap A If using decorative cap cover s this distance may need to be increased Refer to the installation instructions supplied with the decorative cap cover A...

Страница 13: ...d air supply inlet All mechanical air intakes within 10 feet of a horizontal termination cap must be a minimum of 3 feet below termination 3 ft 914 mm 6 ft 1 8 m J On public property clearance above p...

Страница 14: ...or vent component information and dimensions DO NOT mix pipe fittings or joining methods from differ ent manufacturers The pipe is tested to be run inside an enclosed wall There is no requirement for...

Страница 15: ...I V E L E N G T H Y X X X DVP Pipe Effective Length Rise Run Inches Millimeters Inches Millimeters DVP4 4 102 2 3 4 70 DVP6 6 152 4 1 4 108 DVP12 12 305 8 1 2 216 DVP24 24 610 17 432 DVP36 36 914 25 1...

Страница 16: ...ure 12 1 for DVP Figure 12 6 for SLP for information on effective length of pipe components Horizontal terminations are measured to the outside mounting surface flange of termination cap see Figure 4...

Страница 17: ...runs may be level Horizontal termination cap should have a 1 4 inch downward slant to allow any moisture in cap to be released See Figure 4 10 G Vent Diagrams Top Vent Horizontal Termination Two 45 E...

Страница 18: ...X 40 ft 12 2 m See Warning Figure 4 11 Top Vent Horizontal Termination One Elbow Fire Risk When using SLP HRC SS termination cap on top vented fireplaces a one foot minimum vertical vent section is re...

Страница 19: ...1 m 6 ft 1 8 m 4 1 2 ft 1 4 m 14 ft 4 3 m H1 H2 MAX 14 ft 4 3 m V1 H1 H2 MAX 40 ft 12 2 m See Warning Below Fire Risk When using SLP HRC SS termination cap on top vented fireplaces a one foot minimum...

Страница 20: ...t 4 3 m H1 H2 MAX 14 ft 4 3 m V1 V2 H1 H2 MAX 40 ft 12 2 m No specific restrictions on this value EXCEPT V1 V2 H1 H2 CANNOT exceed 40 ft 12 2 m See Warning Below Fire Risk When using SLP HRC SS termin...

Страница 21: ...manual bag Note Be sure to rein stall the exhaust baffle after exhaust restrictor installation Exhaust restrictor Exhaust restrictor Exhaust restrictor Instructions 1 Install the exhaust restrictor ov...

Страница 22: ...2 ft 457 mm 1 2 ft 152 mm 2 ft 610 mm 1 1 2 ft 457 mm 3 ft 914 mm 2 1 2 ft 762 mm 5 ft 1 5 m 3 1 2 ft 1 1 m 7 ft 2 1 m 4 1 2 ft 1 4 m 15 ft 4 6 m H1 MAX 15 ft 4 6 m V1 V2 H1 MAX 40 ft 12 2 m No speci...

Страница 23: ...2 m 3 1 2 ft 1 1 m 6 ft 1 8 m 4 1 2 ft 1 4 m 14 ft 4 3 m H1 H2 MAX 14 ft 4 3 m V1 V2 H1 H2 MAX 40 ft 12 2 m No specific restrictions on this value EXCEPT V1 V2 H1 H2 CANNOT exceed 40 ft 12 2 m Note Us...

Страница 24: ...4 18 V1 MIN H1 MAX V2 MIN H2 MAX V3 MIN 1 1 2 ft 457 mm 4 ft 1 2 m 4 ft 1 2 m 4 ft 1 2 m 3 1 2 ft 1 1 m V1 V2 V3 H1 H2 Maximum 40 ft 12 2 m Note Use SLP Series components only V1 H1 V2 V3 H2 Note The...

Страница 25: ...980 Rev L 10 19 Rear Vent Horizontal Termination Figure 4 20 Figure 4 19 No Elbows H1 9 in 229 mm Maximum Rear Vent Horizontal Termination One 45 Elbow Note Use DVP Series components only Note Use DVP...

Страница 26: ...12 2 m Figure 4 21 H1 MAX V1 MIN H2 H3 MAX H1 H2 H3 MAX 1 1 2 ft 457 mm Back to back elbows 1 ft 305 mm 2 1 2 ft 762 mm 3 1 2 ft 1 1 m 1 ft 305 mm 2 ft 610 mm 5 1 2 ft 1 7 m 5 1 2 ft 1 7 m 2 ft 610 m...

Страница 27: ...7 m 3 ft 914 mm 7 1 2 ft 2 3 m H MAX 7 1 2 ft 2 3 m V1 H1 MAX 40 ft 12 2 m H1 H2 MAX V1 MIN Back to back elbows 1 2 ft 152 mm 2 1 2 ft 762 mm 1 ft 305 mm 4 1 2 ft 1 4 m 2 ft 610 mm 6 1 2 ft 2 0 m 3 f...

Страница 28: ...t 914 mm 6 1 2 ft 2 0 m 2 ft 610 mm 5 1 2 ft 1 7 m 5 ft 1 5 m 10 1 2 ft 3 2 m 3 ft 914 mm 7 1 2 ft 2 3 m 7 ft 2 1 m 14 1 2 ft 4 4 m H1 MAX 7 1 2 ft 2 3 m H1 H2 MAX 14 1 2 ft 4 4 m V1 V2 H1 H2 MAX 40 f...

Страница 29: ...Fire Coaxial to colinear venting con figuration may only be used in existing non combustible chimney Installation in any other venting application could cause fire Prior to installing the gas applian...

Страница 30: ...appliance starting collar with 3 1 2 in self tapping screws See Figure 4 28 Rear Vent Remove the rear seal cap and insulation if equipped Connect the DVP 2SL adapter to the vertically positioned elbow...

Страница 31: ...in 25 mm clearance around vertical sections B Wall Penetration Framing Firestops Combustible Wall Penetration Whenever a combustible wall is penetrated you must frame a hole for the wall shield firest...

Страница 32: ...und the vent Insulation must be kept back from the pipe to prevent overheating Figure 5 3 Installing Ceiling Firestop Figure 5 4 Installing the Attic Shield INSTALL ATTIC INSULATION SHIELDS BEFORE OR...

Страница 33: ...tical position as shown above The heat shield must remain in the vertical position Figure 6 5 Remove the seal cap Figure 6 6 Remove the insulation basket and white insula tion from the center vent pip...

Страница 34: ...er parts of the retaining band toward the center as shown Remove the seal cap Figure 6 11 Discard the seal cap remove and discard the insulation basket Note Once the seal cap has been removed it CANNO...

Страница 35: ...agram shows how to properly position and secure the appliance See Figure 6 13 Nailing tabs are provided to secure the appliance to the framing members Bend out nailing tabs on each side Place the appl...

Страница 36: ...rom rotating Use screws no longer than 1 2 in 13 mm If predrilling screw holes DO NOT penetrate inner pipe WARNING Risk of Fire or Explosion DO NOT break silicone seals on slip sections Use care when...

Страница 37: ...connecting joint after joining sections On horizontal pipe runs it is recom mended that the tape seam is positioned on the bottom side of the vent pipe Only outer pipes need to be sealed All unit coll...

Страница 38: ...very 8 ft 2 44 m after the maximum allowed 25 ft 7 62 m of unsupported rise Vertical runs originating off the rear of the appliance or after any elbow must be supported every 8 ft 2 44 m Horizontal ru...

Страница 39: ...ROOF TO LOWEST DISCHARGE OPENING NOTICE Failure to properly caulk the roof flashing and pipe seams could permit entry of water Caulk the gap between the roof flashing and the outside diameter of the...

Страница 40: ...n Figure 7 16 Heat shields must overlap 1 1 2 in 38 mm mini mum There are two sections of the heat shield One section is factory attached to the wall shield firestop The other section is factory attac...

Страница 41: ...des may require in stallation of a cap shield to prevent anything or anyone from touching the hot cap NOTICE For certain exposures which require superior resistance to wind driven rain penetration a f...

Страница 42: ...ceptacle and reattach the junction box receptacle to the outer shell Electrical Service and Repair WARNING Risk of Shock Label all wires prior to dis connection when servicing controls Wiring errors c...

Страница 43: ...8 2 Intellifire Pilot Ignition IPI Wiring Diagram TRANSFORMER WALL SWITCH 3 VAC PLUG IN BLACK RED BATTERY PACK ORANGE TO BROWN TO BROWN GREEN GROUND TO FIREPLACE CHASSIS WHITE ORANGE IGNITION MODULE 3...

Страница 44: ...d connect to the top fan switch connector 1 4 in male as shown Red Switch Switch Box Red Black Black Green Green White Power Supply Wires White Red Black Green White Minimum 14 3 AWG with Ground Junct...

Страница 45: ...and handling WARNING Risk of Fire DO NOT change valve settings This valve has been preset at the factory WARNING Risk of Fire or Explosion High pressure will damage valve Low pressure could cause exp...

Страница 46: ...e opening the air shutter To adjust loosen the wing nut Care should be taken when adjusting the air shutter so as not to cause the appliance to soot If sooting occurs the air shutter will need to be o...

Страница 47: ...nd louvers 0 IN 0 IN 0 IN SHEETROCK FINISH WALL MATERIAL UP TO 1 2 IN THICK MAY BE COMBUSTIBLE TOP AND SIDES HIGH TEMPERATURE SEALANT 300 F 149 C MIN TOP AND SIDE SEAL JOINT Figure 10 1 Noncombustible...

Страница 48: ...NING 4 12 13 11 32 CEILING Figure 10 7 Non Combustible Zone 1 2 in SHEETROCK OR COMBUSTIBLE MATERIAL 3 1 2 in 1 2 in NON COMBUSTIBLE ZONE Figure 10 6 Non Combustible Mantel Leg or Wall Projections Acc...

Страница 49: ...ed glass panel DO NOT operate the fireplace with the barrier removed Contact your dealer or Hearth Home Technologies if the barrier is not present or help is needed to properly install one 1 Remove de...

Страница 50: ...xed Glass Assembly B Remove the Shipping Materials Remove shipping materials from inside or underneath the firebox The splatter guard is a piece of corrugated material used to protect the appliance du...

Страница 51: ...n in Figure 4 Figure 3 Log 1 Bottom View Log 2 2033 709 Log 2 has holes on the bottom side that will be used for positioning them in the firebox See Figure 5 Place Log 2 on the pins in the front of th...

Страница 52: ...rock jig to prevent the rock from going in between the base pan and burner DO NOT allow any lava rock to fall in the slot and onto the burner Figure 10 Lava Rock and Rock Jig LAVA ROCK ROCK JIG WARNIN...

Страница 53: ...d grooves Figure 12 shows the left side Log 5 in position The right side Log 5 is located by placing the Y Shaped end on the locating grooves of Log 1 and setting the other end on the right side log 2...

Страница 54: ...gure 4 Figure 3 Log 1 Bottom View Log 2 2033 709 Log 2 is used twice in this log set Log 2 also has holes on the bottom side that will be used for positioning them in the firebox See Figure 5 Locate t...

Страница 55: ...he locating pin on the basepan There should be approx a 1 4 inch gap between the end of the log and the firebox The other Log 3 will be placed on the right in a position to mirror the first Log 3 Plac...

Страница 56: ...urner op eration Delayed ignition may occur Remove the burner tube slot cover by removing the shipping screw on the back Keep the burner tube slot cover and screw in the lower cavity of the appliance...

Страница 57: ...a of Log 1 See Figure 15 The Y Shaped section will rest on the left side Log 2 See Figure 16 The left branch of the Y should rest where the burned area of the left Log 2 begins See Figure 17 Figure 15...

Страница 58: ...glass DO NOT operate fireplace with glass removed cracked broken or scratched Replace as a complete assembly Replace the glass door on the appliance Pull out and latch the four glass assembly latches...

Страница 59: ...mm 6 in 152 mm 10 in 254 mm 1 1 2 in 38 mm 5 in 127 mm 12 in 305 mm UP DVP HVS Vent Support DVP WS Wall Shield Firestop DVP FS Ceiling Firestop DVP45 45 Elbow DVP Pipe see chart Effective Height Lengt...

Страница 60: ...38 mm The heat shield is designed to be used on a wall 4 in to 7 1 4 in 102 mm to 184 mm thick If wall thickness is less than 4 in 102 mm the existing heat shields must be field trimmed If wall thickn...

Страница 61: ...Roof Flashing Multi pak Cap Shield DRC RADIUS 13 7 8 in 352 mm 9 1 2 in 241 mm 14 in 356 mm COOL ADDM Cap Shield 11 5 8 in 295 mm 5 3 4 in 146 mm 7 1 8 in 181 mm 12 1 8 in 308 mm DVP BEK2 DVP HPC Cap...

Страница 62: ...133 mm 12 1 2 in 318 mm DVP TVHW VerticalTermination Cap Highwind 14 in 356 mm 12 in 305 mm 12 1 8 in 314 mm 7 1 8 in 181 mm 8 3 4 in 222 mm 1 5 8 in 41 mm 16 7 8 in 429 mm DVP HPC High Performance Ca...

Страница 63: ...m 8 1 8 in 206 mm SLP HRC SS HORIZONTAL TERMINATION CAP When using DVP TB1 termination cap on top vented fireplaces a three foot minimum vertical vent section is required before installing first elbow...

Страница 64: ...s PVI WH60 80 FT PV Wire Harness PVI WH80 100 FT PV Wire Harness PVI WH100 PVI SLP B Power Vent Inline SLP LPC SLP Low Profile Cap Approved for use with PVI SLP B only Note Wire harnesses required to...

Страница 65: ...NUMBER 10 FT PV Wire Harness PVI WH10 20 FT PV Wire Harness PVI WH20 40 FT PV Wire Harness PVI WH40 60 FT PV Wire Harness PVI WH60 80 FT PV Wire Harness PVI WH80 100 FT PV Wire Harness PVI WH100 Note...

Страница 66: ...LP90 90 Elbow Effective Height Length SLP PIPE SLP HVS Horizontal Pipe Support SLP FS Ceiling Firestop SLP WS Wall Shield Firestop 10 7 8 in 276 mm 8 7 8 in 225 mm 1 1 2 in 38 mm 8 11 16 in 220 mm 8 1...

Страница 67: ...he existing heat shields must be field trimmed If wall thickness is greater than 7 1 4 in 184 mm a DVP HSM B will be required Heat Shield Term Cap Minimum Effective Length Maximum Effective Length Tra...

Страница 68: ...14 in 356 mm 14 1 16 in 357 mm 7 1 2 in 192 mm 10 3 4 in 273 mm SLP CCS BK Cathedral Ceiling Support Box Black SLP DCF BK Ceiling Firestop Black SLP TVHW Vertical Termination Cap DVP FBHT Horizontal T...

Страница 69: ...on Manual 2499 980 Rev L 10 19 LINK DV30B Flex Liner Kit DV 46DVA GCL Coaxial Colinear Appliance Connector 768 380A Stainless Steel Flex Pipe DVP 2SL Adapter COAXIAL to COLINEAR VENTING Figure 12 11 C...

Страница 70: ...ied with the fan kit to operate your fan See your dealer if you have questions Printed in U S A Copyright 2019 Heat Glo a brand of Hearth Home Technologies 7571 215th Street West Lakeville MN 55044 ww...