Symptoms

Possible Causes

Corrective Action

IntelliFire™ Plus System

Main Closes/ Pilot open, 5 seconds later pilot 

sparking with Fan ON.  If condition persists for 

60 seconds, 8K-1 locks out with 3 LED alarm.

  Pilot Rectification Failure

1.  Verify that black wire on IPI wire harness is prop-

erly grounded to the appliance chassis.   

2.  Verify that pilot is not being compromised by draft 

such  that  it  fails  to  rectify.    With  the  glass  as-

sembly in place, verify that the pilot flame is en-

gulfing the flame sensing rod on the left side of 

the pilot hood.  With a multi-meter, verify that the 

current  in  series  between  the  module  and  the 

sense lead is at least 0.14 microamps.  

3.  Verify that line inlet pressure is within range on 

rating plate and correct pilot orifice is in pilot.  

4.   If #1-4 are correct, replace IPI module.

No power to the module when fan is on (after 

120 sec pre-purge).

Blocked Flue/Insufficient Draft

1.  Verify the teflon pressure tube is connected be-

tween fan impeller housing and vacuum switch.  

2.   Verify that wiring within PVLP-SLP-AU is correct 

and that the fan operates.

3.  Verify that the venting is connected and sealed 

properly.  

4.  Verify that the vent termination is not blocked.  
5.  If #1 thru #4 are complete, connect black and red 

wires to bypass vacuum switch.  If malfunction 

is  corrected,  lock-out  system  until  the  vacuum 

switch can be replaced.

Main Closes, 5 seconds later pilot sparking with 

Fan ON.   If condition persists for 60 seconds, 

8K-1 locks out with 3 LED alarm.

Shorted Pilot Sense

1.  Verify  that  the  white  sensor  lead  is  properly 

 

     connected to the S-terminal on the module.   
2.  Check for soot deposits on the pilot sense rod,

 

     adjacent shielding, or logs.  If so, clean affected 

 

      parts. 
3.  Verify that the white sense lead from the pilot is 

 

       not damaged or melted within the firebox or valve 

 

     compartment.  Replace pilot if damage exists. 

Main Closes, 5 seconds later pilot sparking with 

Fan ON.   If condition persists for 60 seconds, 

8K-1 locks out with 3 LED alarm.

Disconnected Pilot Sense

Verify that white sensor lead is properly connected 

to the S-terminal and the orange ignitor lead is con-

nected to the I-terminal on the module

If given ignition command in both ON and RE-

MOTE modes, system immediately locks-out 

with 3 LED alarm.  Does not spark or attempt 

to ignite.

Pre-Existing/False Pilot Flame

Check for pre-existing pilot flame.  If so, the valve is 

defective and should be replaced.  

Pilot rectifies, burner begins to light, but has a 

difficult time fully lighting.

Draft from back of firebox is too  strong due to 

power vent.

Make sure air baffle is properly adjusted. If it is ad-

justed properly, place ember material along the back 

side  of  the  ports  that  are  experiencing  the  difficult 

lighting.  This will block a portion of the strong draft.

E.  PVLP-SLP-AU Troubleshooting

Please contact your Hearth & Home Technologies dealer 

with any questions or concerns. 

For the location of your nearest Hearth & Home 

Technologies dealer, 

please visit www.hearthnhome.com.

Hearth & Home Technologies 

 

7571 215th Street West, Lakeville, MN 55044

www.hearthnhome.com

Содержание PVLP-SLP-AU

Страница 1: ...table Vent Configurations 8 D Setting the PVLP SLP AU Baffle Adjustment 8 3 Framing and Clearances A Framing and Clearances 9 B Termination Cap Clearances 11 C Installing Vent Cap 12 4 Electrical Info...

Страница 2: ...d with models configured with the PVLP SLP AU The wired wall switch feature is required to be used with models configured with the PVLP SLP AU B Installation of PVLP SLP AU 1 INSTALLATION PRECAUTIONS...

Страница 3: ...irement between appliance and PVLP SLP AU on all models Combustible materials surrounding pipe may overheat 1 A minimum length of venting is required between the appliance and the PVLP SLP AU This min...

Страница 4: ...ent section directly off the appliance B Vent Pipe Regulations continued MODEL MINIMUM VENTING BETWEEN APPLIANCE AND PVLP SLP AU 6X AU No minimum vertical venting required for rear vent appliances Mus...

Страница 5: ...ETER DVP PIPE MAX ELBOWS 45 90 MAX TOTAL VENT RUN FT MAX VERT DROP FT 12 45 or 6 90 90 ft 27 43 m 12 ft 3 66 m See table in Section 2 C ADAPTER KITS PART NUMBER PART DESCRIPTION DVP SLP24 Adapts from...

Страница 6: ...piping is required between the appliance and the PVLP SLP AU with certain appli ance models See Table 2 1 See Chart in Section 2 C Venting Length Model Categories and Length Requirements by Terminatio...

Страница 7: ...straight vertical DVP pipe directly off appliance followed by 90 degree elbow and DVP 2SL adapter on these models MEZZO1000 AUB MEZZO1300 AUB MEZZO1300ST AUB MEZZO1600 AUB Combustibles surrounding pi...

Страница 8: ...6 10 m 30 ft 9 14 m 40 ft 12 19 m 50 ft 15 24 m 60 ft 18 29 m 70 ft 21 34 m 80 ft 24 38 m 90 ft 27 43 m 1 2 3 4 5 6 7 8 9 10 11 12 ALLOWABLE VENT RUNS Distance from PVLP SLP AU to Appliance Maximum Al...

Страница 9: ...mm 121mm 241mm 9 1 2 in 12 1 2 in 318mm 159mm 6 1 4 in 1 1 2 in 38mm Front View Without Cover Front View With Cover Side View Back View Top view 13 IN 330 mm 10 IN 254 mm Framing Dimensions 1 Construc...

Страница 10: ...lat roof an enclosure similar to the one shown in Figure 3 4 will need to be constructed 1 in 25mm 1 1 2 in 38mm 0 2 in 51mm 20 3 4 in 527mm 12 in 305mm Figure 3 4 0 in 0 in 0 in 0 in 1 in 25mm to sid...

Страница 11: ...es 32 MJ h and below 300 355 Appliances from 32 MJ h to 53 MJ h 300 410 Appliances 53 MJ h and above 300 460 c From a return wall or external corner 500 300 d From a gas meter M 1000 1000 e From an el...

Страница 12: ...Figure 3 10 NOTE The PVLP SLP AU may be painted to a desired color as long as the paint selected has sufficient temperature and environmental ratings Thoroughly sand the existing coating prior to pai...

Страница 13: ...e 3 12 Figure 3 13 Figure 3 14 5 Attached the red and white wires to the pressure switch See Figure 3 11 NOTE Make sure there is not excess wire extending through the back cap cover If extra wire leng...

Страница 14: ...to measure the distance from the front cover to the flange on the air baffle See Figure 3 15 9 Reinstall the exhaust housing assembly into the cap after the wiring and baffle adjustment have been com...

Страница 15: ...ECTION B SECURE TO BUILDING EXTERIOR USING TOP 2 AND BOTTOM 2 MOUNTING HOLES Figure 3 18 BEK Assembled 11 Assemble the PVLP BEK kit Bend the two sections of the PVLP BEK kit as shown in Figure 3 17 12...

Страница 16: ...e See Figure 3 24 25 Reinstall the cap cover using the four scews removed earlier SILICONE with a minimum of 300 F continuous exposure rating ALL 4 SIDES SILICONE with a minimum of 300 F continuous ex...

Страница 17: ...ule Fireplace Power Supply USA MALE PLUG Power Input Fireplace Appliance Figure 4 1 Wiring Diagram Figure 4 1 below shows a wiring diagram of the PVLP SLP AU wiring harness Figure 4 2 shows a photo of...

Страница 18: ...on cap to female plug number 2 in Figure 4 2 5 Unplug 6V transformer from fireplace power cord Run plug for 6V from timer control junction box inside the fireplace and plug 6V transformer in number 4...

Страница 19: ...es B Power Vent Operating Instructions After installation of the power vent follow the operation instructions below IPI Plus RC300 1 Turn the wall switch ON NOTE A 100 120 second pre purge will begin...

Страница 20: ...repair to the power vent assembly make sure electrical power is disconnected to the appliance 1 Remove front cap cover and set aside See Figure 5 2 if cap has to be serviced from inside the building r...

Страница 21: ...21 Hearth Home Technologies Power Vent Low Profile PVLP SLP AU Instructions 4052 902 Rev C 10 19 Figure 5 7 Figure 5 8 Figure 5 9 Figure 5 10...

Страница 22: ...ater pilot sparking with Fan ON If condition persists for 60 seconds 8K 1 locks out with 3 LED alarm Shorted Pilot Sense 1 Verify that the white sensor lead is properly connected to the S terminal on...

Отзывы: