7 Cleaning and maintaining the heating system – Procedure
83
C
HECKING
AND
CLEANING
THE
LAMBDA
SENSOR
1.
Allow the fire in the boiler to burn out and cool off.
2.
Unscrew the union nut (2) with a pipe wrench.
3.
Remove the lambda sensor (1) and the insulating washer
underneath it from the connection nozzle (3).
4.
Brush off the lambda sensor (1) with a brass brush.
5.
Clean out any deposits found inside the connection nozzle (3).
6.
Reinstall the lambda sensor (1) in the reverse sequence.
The inspection of the lambda probe is completed.
C
LEANING
THE
FLUE
SENSOR
Caution!
See the “General safety instructions” section in this chapter.
Figure 7/10 - Cleaning the lambda probe
1
2
3
Caution!
To clean the lambda sensor, use a fine brass brush instead of a steel
brush.
Steel bristles will damage the lambda sensor.
Caution!
When reinstalling the lambda sensor, make sure its seal is intact.
Use a pipe wrench to tighten the union nut (1). Do not tighten the
lambda sensor excessively. Never tighten the lambda sensor by the
shaft body.
Caution!
See the “General safety instructions” section in this chapter.