6 Using the heating system – Displaying information
65
A
CCESSIBLE
INFORMATION
Preset target values, current actual values and analyses:
E
XAMPLE
CALCULATION
FOR
OPERATIONAL
READINESS
450 operating hours at 20% readiness equates to 90 hours with
the boiler temperature above 88 ?
.
Consequence: The boiler would thus have been
overheated
for 90
hours.
Display
Description
Authorisation
TK S
[°C]
82.0
TK I
[°C]
73.4
•
Maximum required boiler water temperature
•
Actual value
Operator
TS I
[°C] 23.8
•
Current accumulator temperature
No access
TK min
[°C]
60.0
TS min
[°C]
45.0
•
Required minimum boiler temperature
•
Required minimum accumulator temperature
Operator
TA I
[°C]
23.0
Peak value
226.0
•
Current exhaust temperature
•
Highest flue gas temperature reached
No access
O2 S
[%]
6.0
O2 I
[%]
5.6
•
Preset target value for residual oxygen
•
Current actual value for residual oxygen
Manufacturer
CO2 S
[%]
15.4
CO2 I
[%]
15.8
•
Target value for carbon dioxide
•
Calculated actual value for carbon dioxide
No access
Lambda [/]
1.9
ETA-F [%]
90.0
•
Current excess air coefficient
•
Current combustion efficiency
No access
Operating hours
[h]
•
Cumulative operating hours in
“
Heat
production on
”
mode.
No access
Operational
readiness
[%]
0.0
•
Display of the percentage of operating hours
during which the boiler temperature was above
88°C (*) during the last 500 hours.
No access
Last fault
•
Most recent fault since the last query
Operator
Table 6/1 - Target value information
(*) If this value is too high, there is a danger of excessive soiling of
the boiler and the chimney!
Danger of fire in the chimney and flue!
See the following example calculation.