6.2.1 Defining your own configuration combinations
Only one configuration entry is available. The special identification format
(special format) must be used for this. The manufacturer
−
specific data
specifies the contents and thus also the length of the input data and is 2 bytes
in length.
CFG entry no.
Meaning
Contents
0
channel 1
special format with inputs and outputs, maximum 9 words
output, maximum 13 words input, 2 bytes comment length
(data)
The following input and output data can be configured for the cyclical data
communication. The choice of which data is actually transferred is
communicated via the manufacturer
−
specific data of the special identification
format.
Configuration
manufacturer
−
specific data
Length of cyclical data
inputs
Length of cyclical data
outputs
Contents of cyclical
data
Byte no. Bit no.
(words)
(words)
Input values:
0
0
1(2)
Gross
0
1
1(2)
Net
0
2
1(2)
Max
0
3
1(2)
Min
0
4
1(2)
Peak
−
to
−
peak
0
5
1
Status1
0
6
2
Status2
Output values:
1
0
1
Control word
1
1
1(2)
Limit value level 1
1
2
1(2)
Limit value level 2
1
3
1(2)
Limit value level 3
1
4
1(2)
Limit value level 4
Tab 6.3:
Selecting the data content via the manufacturer
−
specific data
The length of the input data is the sum of all the data lengths selected for the
communication in words. When selecting the 32 bit format and the float format
for measured values, the length values in brackets must be used.