![HBM ML77B Скачать руководство пользователя страница 28](http://html1.mh-extra.com/html/hbm/ml77b/ml77b_operating-manual_2111902028.webp)
Profibus
28
A00760_09_E00_00
HBM: public
ML77B
Mode1
Bit
Name
Meaning
0
GW1
Status of limit switch 1
1
GW2
Status of limit switch 2
2
GW3
Status of limit switch 3
3
GW4
Status of limit switch 4
4
Res
Reserved
5
Res
Reserved
6
CHN_ERR
Error in channel
7
CHANGE
Changed scaling of measured values
8
PAR1
Active parameter set bit 1
9
PAR2
Active parameter set bit 2
10
PAR3
Active parameter set bit 3
11
PAR4
Active parameter set bit 4
12..14
Res
Reserved
15
MODE
1
The parameter set number is binary coded in 3 bits:
Bit 8
Bit 9
Bit 10
Parameter set no.
0
0
0
1
1
0
0
2
0
1
0
3
1
1
0
4
0
0
1
5
1
0
1
6
0
1
1
7
1
1
1
8
9.1.4
Channel status for 8-channel device
Mode0
Bit
Name
Meaning
0
GW1
Status of limit switch 1
1
GW2
Status of limit switch 2
2
GW3
Status of limit switch 3
Содержание ML77B
Страница 1: ...Operating Manual English ML77B Profibus Interface...
Страница 6: ...6 A00760_09_E00_00 HBM public ML77B...