Hayward HRCK2A Скачать руководство пользователя страница 1

USE ONLY HAYWARD GENUINE REPLACEMENT PARTS

HRSLCSSPLMNTIOM Rev A

Page 1 of 42 

Hayward Flow Control
1-888-HAY-INDL (1-888-429-4635)

www.haywardflowcontrol.com

TO PREVENT POTENTIAL INJURY OR DAMAGE TO PROPERTY, READ THIS MANUAL CAREFULLY AND COMPLETELY. 

INSTALLATION, OPERATION AND 

MAINTENANCE INSTRUCTIONS

LCS Products Supplement  

to HRSN2 through HRSN6 Series  

Low Voltage and Single Phase Products

Back to TOC

Содержание HRCK2A

Страница 1: ...88 HAY INDL 1 888 429 4635 www haywardflowcontrol com TO PREVENT POTENTIAL INJURY OR DAMAGE TO PROPERTY READ THIS MANUAL CAREFULLY AND COMPLETELY INSTALLATION OPERATION AND MAINTENANCE INSTRUCTIONS LC...

Страница 2: ...tions WARNING Failure to bond all electrical equipment to system structure will increase risk for electrocution and could result in injury or death To reduce the risk of electric shock see installatio...

Страница 3: ...AR8 refer to the IOM for the respective 3 Phase unit These instructions are specific to low voltage and single phase products only Important Safety Instructions 2 Table of Contents 3 LCS Supplement to...

Страница 4: ...ED indicators to show Power Running Open and Fully Open Running Closed and Fully Closed positions This version is available on HRSN3 thru HRSN6 Series 24v 120v 230v On Off and Proportional Control act...

Страница 5: ...0VAC HRCK2A 6A XTS TS LCS CK 7 Mod 24VDC VAC HRCP3A 6A XTS TS LCS CP 7 Mod 120 230VAC HRCP3A 6A XTS TS LCS CP 7 On Off 24VDC VAC HRCL3A 6A XTS TS LCS CL 8 On Off 120 230VAC HRCL3A 6A XTS TS LCS CL 8 O...

Страница 6: ...Local Control Device This series is designed to operate in Local mode control knobs or buttons located on the face of the LCS which is an integral part of the actuator or in Remote mode which utilize...

Страница 7: ...is feature allows operation of the actuator WITHOUT having an existing PLC or BAS based analog controller while also providing operability with existing external controls Inside the actuator LCS packa...

Страница 8: ...l Station LCS to facilitate operating the actuator locally Having this feature allows operation of the actuator WITHOUT having an existing PLC or BAS based analog controller while also providing opera...

Страница 9: ...allows operation of the actuator WITHOUT having an existing PLC or BAS based analog controller while also providing operability with existing external controls Inside the actuator LCS package you wil...

Страница 10: ...device The manual handwheel may be used to reposition the actuator while in this mode however if an active external signal is present the actuator WILL reposition as a function of that control signal...

Страница 11: ...N RE LO REMOTE LOCAL all actuators When the RE LO push button is pressed the mode switches from Local to Remote and back with each successive press of the push button REMOTE When the unit is in Remote...

Страница 12: ...uators Sets the actuator to respond to field generated control signals In this mode the POSITION KNOB left side has NO affect on the positioning of the actuator All actuator movement is controlled by...

Страница 13: ...to field generated control signals In this mode the POSITION KNOB left side has NO affect on the positioning of the actuator All actuator movement is controlled by the external signal device The manu...

Страница 14: ...uator should NOT move I If it does IMMEDIATELY remove power from the actuator to STOP movement II Check control wiring Reference the Actuator IOM Correct if necessary and repeat step 3 B Terminal 7 is...

Страница 15: ...p on the face of the LCS 6 If the actuator does NOT stop at the correct positions fails to move in the correct directions or on torque switch units fails to stop movement when the torque switch levers...

Страница 16: ...rom midpoint IMMEDIATELY remove power from the actuator to STOP movement Place a meter in series with terminal 3 ref and the wire coming from the field controller it MUST read 12mA If it does NOT chec...

Страница 17: ...ator movement as a check of the system D On HRCK5A 6A units with torque switches during CCW travel movement depress the lever on the UPPER torque switch to interrupt actuator movement as a check of th...

Страница 18: ...ent C Terminal 7 is control voltage OUT of the actuator and feeds the Field control panel PLC With the MODE switch in REMOTE measure the voltage between terminals 2 COM NEG NEU 7 HOT POS L1 and confir...

Страница 19: ...actuator does NOT stop at the correct positions fails to move in the correct directions or on torque switch units fails to stop movement when the torque switch levers are depressed IMMEDIATELY STOP t...

Страница 20: ...remove power from the actuator to STOP movement C Verify that the remote move command is transmitting a 4mA control signal to the actuator Insert a 4 20 signal monitor in series with terminal 3 IN Co...

Страница 21: ...to the Table of Contents for the section to reference for the corrective action needed 8 Depress the LCS Mode switch so it turns OFF It will then be in LOCAL mode A The actuator should NOT move 9 Dep...

Страница 22: ...on A A The actuator should NOT move I If it does IMMEDIATELY remove power from the actuator to STOP movement II Check control wiring Reference the Actuator IOM Correct if necessary and repeat step 4 B...

Страница 23: ...will light up on the face of the LCS 7 If the actuator does NOT stop at the correct positions fails to move in the correct directions or on torque switch units fails to stop movement when the torque s...

Страница 24: ...SIG IN it MUST read 12mA i If it does NOT check the polarity of the incoming analog signal to make sure it is 12mA Repeat step 4 II If the actuator moves momentarily and then STOPS at the mid stroke p...

Страница 25: ...tch to interrupt actuator movement as a check of the system F When the actuator reaches its full CCW end of travel position the GREEN LED indicator will remain ON steady on the face of the LCS 7 If th...

Страница 26: ...disconnect 4 Be sure there are NO REMOTE movement commands active and place the LCS Mode switch in the REMOTE position A A The actuator should NOT move I If it does IMMEDIATELY remove power from the a...

Страница 27: ...uator does NOT stop at the correct positions fails to move in the correct directions or on torque switch units fails to stop movement when the torque switch levers are depressed IMMEDIATELY STOP the o...

Страница 28: ...3 SIG IN it MUST read 12mA i If it does NOT check the polarity of the incoming analog signal to make sure it is 12mA Repeat step 4 II If the actuator moves momentarily and then STOPS at the mid stroke...

Страница 29: ...ay indicating a move OPEN or CCW Upon reaching end of travel the grn FO LED will be on steady and the display will show a graphic of an OPEN valve D On HRCK3A 4F units with torque switches during CCW...

Страница 30: ...running in the CCW direction the LCD display will flash the percentage of full OPEN in the center of the screen and the grn FO LED will be flashing There will also be a small UP arrow just to the rig...

Страница 31: ...USE ONLY HAYWARD GENUINE REPLACEMENT PARTS HRSLCSSPLMNTIOM Rev A Page 31 of 42 Hayward Flow Control 1 888 HAY INDL 1 888 429 4635 www haywardflowcontrol com NOTES Back to TOC...

Страница 32: ...MA 4X Protection NEMA 4X Cover Seal Captured Cover Screws UV Impact resistant protective Indicator Cover ISO5211 Mounting System ISO5211 Double Square Female Drive Socket Inside the actuator Easily ac...

Страница 33: ...3 12 turns 90 11 3 5 1 Mod LV 8 58 218 4 M8 1 25 X 20mm Deep F07 2 756 70 HRCK2R on off LV 6 38 162 4 93 125 2 20 56 1 40 36 4 22 107 6 63 170 3 25 83 0 551 14 0 78 20 4 M6 1 0 X 18mm Deep F05 1 969 5...

Страница 34: ...ustom interfaces Worm Override Shaft Aluminum Casting NEMA 4X Protection Aluminum Casting NEMA 4X Protection NEMA 4X Cover Seal Captured Cover Screws UV Impact resistant protective Indicator Cover NEM...

Страница 35: ...5 X 20mm D F10 4 02 102 7 76 197 14 5 turns 90 51 23 HRSN4B 12 64 321 7 87 200 8 78 223 4 06 103 10 31 262 5 91 150 11 69 297 1 063 27 2 17 55 4 M12 1 75 X 25mm D F12 4 92 125 7 76 197 14 5 turns 90 5...

Страница 36: ...custom interfaces Worm Override Shaft Torque Switches Aluminum Casting NEMA 4X Protection Aluminum Casting NEMA 4X Protection Aluminum Casting NEMA 4X Protection Lower casting has been rotated for cl...

Страница 37: ...6 3 35 85 4 M20 2 5 X 35mm D F16 6 50 165 11 42 290 36 5 turns 90 167 76 HRSN5B 20 94 532 9 84 250 8 46 215 4 57 116 11 54 293 11 89 302 7 17 182 1 811 46 3 35 85 4 M20 2 5 X 35mm D F16 6 50 165 11 42...

Страница 38: ...stom interfaces Worm Override Shaft Aluminum Casting NEMA 4X Protection Aluminum Casting NEMA 4X Protection NEMA 4X Cover Seal Captured Cover Screws UV Impact resistant protective Indicator Cover NEMA...

Страница 39: ...X 20mm D F10 4 02 102 7 76 197 14 5 turns 90 51 23 HRSN4B 12 64 321 7 87 200 8 78 223 4 06 103 10 31 262 5 91 150 11 69 297 1 063 27 2 17 55 4 M12 1 75 X 25mm D F12 4 92 125 7 76 197 14 5 turns 90 51...

Страница 40: ...custom interfaces Worm Override Shaft Torque Switches Aluminum Casting NEMA 4X Protection Aluminum Casting NEMA 4X Protection Aluminum Casting NEMA 4X Protection NEMA 4X Cover Seal Captured Cover Scre...

Страница 41: ...182 1 811 46 3 35 85 4 M20 2 5 X 35mm D F16 6 50 165 11 42 290 36 5 turns 90 167 76 HRSN5B 20 94 532 9 84 250 8 46 215 4 57 116 11 54 293 11 89 302 7 17 182 1 811 46 3 35 85 4 M20 2 5 X 35mm D F16 6...

Страница 42: ...E ONLY HAYWARD GENUINE REPLACEMENT PARTS HRSLCSSPLMNTIOM Rev A Page 42 of 42 Hayward Flow Control 1 888 HAY INDL 1 888 429 4635 www haywardflowcontrol com This page intentionally left blank Back to TO...