Temperature/Resistance /Voltage

All Hayward controls use a 10K thermistor sensors.  When disconnected from the

control, the sensor will read 10K ohms at 25ºC/77ºF.  Refer to the chart below for

the resistance at other  temperatures.  For a given temperature, the resistance

reading should be accurate to  ±1%.  For a given resistance reading, the tempera-

ture reading should be accurate to ±0.5ºF.  All voltage measurements (DC) must

be made with the sensor connected to the control and should be accurate to ± 2%.

°F

Ohms

Volts °F

Ohms

Volts

°F

Ohms

Volts

°F

Ohms

Volts

1

82,719

   

4.46

41

25,391

   

3.59

81

9,076

     

2.38

121

3,679

     

1.34

2

80,142

   

4.45

42

24,704

   

3.56

82

8,861

     

2.35

122

3,602

     

1.32

3

77,656

   

4.43

43

24,037

   

3.53

83

8,651

     

2.32

123

3,527

     

1.30

4

75,255

   

4.41

44

23,391

   

3.50

84

8,447

     

2.29

124

3,454

     

1.28

5

72,937

   

4.40

45

22,764

   

3.47

85

8,249

     

2.26

125

3,382

     

1.26

6

70,698

   

4.38

46

22,156

   

3.45

86

8,056

     

2.23

126

3,312

     

1.24

7

68,535

   

4.36

47

21,566

   

3.42

87

7,867

     

2.20

127

3,244

     

1.22

8

66,447

   

4.35

48

20,993

   

3.39

88

7,684

     

2.17

128

3,177

     

1.21

9

64,428

   

4.33

49

20,438

   

3.36

89

7,506

     

2.14

129

3,112

     

1.19

10

62,479

   

4.31

50

19,900

   

3.33

90

7,333

     

2.12

130

3,049

     

1.17

11

60,595

   

4.29

51

19,377

   

3.30

91

7,164

     

2.09

131

2,987

     

1.15

12

58,774

   

4.27

52

18,870

   

3.27

92

6,999

     

2.06

132

2,926

     

1.13

13

57,014

   

4.25

53

18,377

   

3.24

93

6,839

     

2.03

133

2,867

     

1.11

14

55,313

   

4.23

54

17,899

   

3.21

94

6,683

     

2.00

134

2,809

     

1.10

15

53,669

   

4.21

55

17,435

   

3.18

95

6,530

     

1.98

135

2,752

     

1.08

16

52,078

   

4.19

56

16,985

   

3.15

96

6,382

     

1.95

136

2,697

     

1.06

17

50,541

   

4.17

57

16,548

   

3.12

97

6,238

     

1.92

137

2,643

     

1.05

18

49,054

   

4.15

58

16,123

   

3.09

98

6,097

     

1.89

138

2,591

     

1.03

19

47,616

   

4.13

59

15,711

   

3.06

99

5,960

     

1.87

139

2,539

     

1.01

20

46,225

   

4.11

60

15,310

   

3.02

100

5,827

     

1.84

140

2,489

     

1.00

21

44,879

   

4.09

61

14,921

   

2.99

101

5,697

     

1.81

141

2,440

     

0.98

22

43,577

   

4.07

62

14,543

   

2.96

102

5,570

     

1.79

142

2,392

     

0.97

23

42,318

   

4.04

63

14,176

   

2.93

103

5,446

     

1.76

143

2,345

     

0.95

24

41,099

   

4.02

64

13,820

   

2.90

104

5,326

     

1.74

144

2,299

     

0.93

25

39,919

   

4.00

65

13,473

   

2.87

105

5,208

     

1.71

145

2,254

     

0.92

26

38,777

   

3.97

66

13,136

   

2.84

106

5,094

     

1.69

146

2,210

     

0.90

27

37,671

   

3.95

67

12,809

   

2.81

107

4,982

     

1.66

147

2,167

     

0.89

28

36,601

   

3.93

68

12,491

   

2.78

108

4,873

     

1.64

148

2,125

     

0.88

29

35,565

   

3.90

69

12,182

   

2.75

109

4,767

     

1.61

149

2,084

     

0.86

30

34,561

   

3.88

70

11,882

   

2.72

110

4,664

     

1.59

150

2,044

     

0.85

31

33,590

   

3.85

71

11,589

   

2.68

111

4,563

     

1.57

151

2,005

     

0.84

32

32,648

   

3.83

72

11,305

   

2.65

112

4,464

     

1.54

152

1,966

     

0.82

33

31,737

   

3.80

73

11,029

   

2.62

113

4,368

     

1.52

153

1,929

     

0.81

34

30,853

   

3.78

74

10,761

   

2.59

114

4,274

     

1.50

154

1,892

     

0.80

35

29,998

   

3.75

75

10,500

   

2.56

115

4,183

     

1.47

155

1,856

     

0.78

36

29,169

   

3.72

76

10,246

   

2.53

116

4,094

     

1.45

156

1,821

     

0.77

37

28,365

   

3.70

77

9,999

     

2.50

117

4,007

     

1.43

157

1,787

     

0.76

38

27,587

   

3.67

78

9,758

     

2.47

118

3,922

     

1.41

158

1,753

     

0.75

39

26,832

   

3.64

79

9,525

     

2.44

119

3,839

     

1.39

159

1,720

     

0.73

40

26,100

   

3.61

80

9,297

     

2.41

120

3,758

     

1.37

160

1,688

     

0.72

Electronic Solar Control Center

Operation and Installation

Manual

AQ-SOL-LV

AQ-SOL-LV-TC

AQ-SOL-LV-SP

092008F RevG

Copyright © 2010 Hayward Inc.

www.haywardnet.com

620 Division St.

Elizabeth, NJ  07207

Aqua Solar

Содержание Aqua Solar

Страница 1: ...95 136 2 697 1 06 17 50 541 4 17 57 16 548 3 12 97 6 238 1 92 137 2 643 1 05 18 49 054 4 15 58 16 123 3 09 98 6 097 1 89 138 2 591 1 03 19 47 616 4 13 59 15 711 3 06 99 5 960 1 87 139 2 539 1 01 20 4...

Страница 2: ...vice or repair please contact the place of purchase or the nearest Hayward authorized warranty service center For more information please contact the Hayward Technical Service Support Center or visit...

Страница 3: ...ain circuit PCB may have a problem 8 Aux Sensor LED flashing Err on the Aux temperature display Flashing indicates a probable short circuit in the AUX sensor or wiring The digital pool temperature dis...

Страница 4: ...Troubleshooting 1 Power LEDoff Check main power circuit breakers Check to see if theAqua Solar power is connected to the LOAD side of the filter pump timer in which case theAqua Solar will only be on...

Страница 5: ...ins COOLING Ahigh voltage relay for filter pump control is usually required to imple ment this function If Cooling is enabled theAqua Solar will cool the pool by turning on the filter pump and diverti...

Страница 6: ...s detected with theAUX sensor short circuit only when used for recirculate freeze protection AQ SOL LV TC The Aqua Solar will automatically ensure that the filter pump is running before turning on the...

Страница 7: ...in connectors see diagram above for location of connec tors If the valve operates opposite to the way it is supposed to disconnect and plug into the other connector 7 Booster Pump Pool Sweep Filter Pu...

Страница 8: ...he shields to the Aqua Solar s ground screw High Voltage Relay Output Wiring Amaximum of two high voltage relays industry standard may be added to theAQ SOL LV TheAQ SOL LV TC model comes with one rel...

Отзывы: