HAYWARD POOL PRODUCTS, INC.

Indoor Vent Installation Instructions

Negative Pressure (Vertical) Venting Kits

for Universal H-Series (Forced-Draft) Heaters

IMPORTANT NOTES:

1. This kit is intended to be used only with Hayward Universal H-Series (forced-draft) gas heater models built after Apr 30, 

2008, serial # 21130804103872001.  These heaters may be identified by inspection of the heater rating plate.  The model 

number should match one of those listed in Table 1, and on models H250FD, H350FD, and H400FD, the serial number 

should indicate a manufacture date of Apr 2008 or later.  If the manufacture date is Apr 2008, the serial number must be 

greater than 03872.  Table 2 may be used to extract the date of heater manufacture based on heater serial number.  If it is 

necessary to install this kit in a heater built before the above listed manufacture date, a separate kit is needed to update 

your  heater.    Install  kit  FDXLRGK1250,  FDXLRGK1350,  or  FDXLRGK1400  (depending  on  your  heater  model)  before 

installing the indoor vent kit.  All models H150FD, H200FD, and H300FD are compatible with this kit.

 

2. This instruction sheet is intended for only the heater service parts kits listed in Table 1.

 

3. This  kit  enables  indoor  installations  where  the  exhaust  vent  pipe  termination  is  required  to  be  vertically  terminated  a 

minimum of 3 ft above the roof and a minimum of 2 ft above any portion of a building within 10 ft horizontally.  This kit does 

not  allow  horizontal  vent  termination.    Please  refer  to  the  instructions  for  kit  part  numbers  UHXPOSHZ1150, 

UHXPOSHZ1200, UHXPOSHZ1250, UHXPOSHZ1300, UHXPOSHZ1350, and UHXPOSHZ1400 for other indoor venting 

applications.    

1301666601 rev B

Page 1 of 10

TABLE 1

TABLE 2

Serial Number Format

Year (y)

21130ymm1xxxxx001

7=2007                     

8=2008                     

9=2009                     

0=2010

01=Jan                    

02=Feb                        

03=Mar                             

04=Apr                      

05=May                    

06=Jun

07=Jul                             

08=Aug                         

09=Sep                         

10=Oct                              

11=Nov                         

12=Dec

Month (mm)

Note:  "xxxxx" indicates the serial number.

WARNING

Failure  to  comply  with  the  installation  instructions  in  this  instruction  sheet  may  result  in 

equipment  damage,  fire,  asphyxiation,  or  carbon  monoxide  poisoning.    Exposure  to 

products of incomplete combustion (carbon monoxide) can cause cancer, birth defects, or other reproductive harm.

4. Installation of this kit should be conducted only by a qualified technician, specifically trained and experienced in the 

installation of this type of heating equipment.  Some states or provinces require that installers be licensed.  If this is the 

case in the state or province where the heater is located, the contractor must be properly licensed.

 

5.  This kit should be installed in accordance with all local and state codes.  The installation of this kit must conform to 

the  latest  edition  of  the  National  Fuel  Gas  Code  (ANSI  Z223.1/NFPA  54),  and  with  the  requirements  of  the  local 

authority having jurisdiction.  Design certification of this kit is in compliance with ANSI Z21.56/CSA 4.7.  For Canadian 

installations, this kit is to be installed in accordance with the standard CAN/CGA B149.1 - Installation Codes for Gas 

Burning Appliances and Equipment and/or local codes.

EN

G

LIS

H

Part Number

Description

For Use With                        

Heater Models

Vent Pipe Limitations

Vent Pipe Material

Vent Termination 

Requirement

UHXNEGVT1150

H150FD

UHXNEGVT1200

H200FD

UHXNEGVT1250

H250FD

UHXNEGVT1300

H300FD

UHXNEGVT1350

H350FD

UHXNEGVT1400

H400FD

Indoor Vent Adapter 

Kit, Negative Pressure, 

Vertical Venting 

Applications

50 ft max vertical height,                                            

25 ft max horizontal length 

(horizontal length cannot exceed 

1/2 of vertical height),                                                 

3 elbows max 

Single or Double Wall 

Galvanized Non-

Sealed Vent Pipe

Vertical Only, 

Termination Above Roof 

of House/Building