Split-Core Current Transducer

4-20mA Output

Installer’s Specifications

Sensor Power 

30mA (max.)@12-30VDC

Insulation Class 

600VAC rms (UL), 300VAC rms (CE)

Frequency 

50/60Hz

Temperature Range 

-15° to 60°C (5° to 140°F)

Humidity Range 

10-90% RH non-condensing

Amperage Range 

0-30/60/120 Amps (slide-switch selectable)

Output  

4-20mA DC

Hysteresis 

10% of setpoint, typical

Off-State Leakage 

1+ MΩ

Safety 

UL 508, IEC 61010-1: 2001 CAT III

Specification Note: For CE compliance, conductor shall be insulated according to IEC 61010‑1:2001, 

Installation Category III or equivalent.

The product design provides for basic insulation only. 

HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH

•  Follow safe electrical work practices. 

See NFPA 70E in the USA, or applicable local codes.

•  This equipment must only be installed and serviced by qualified electrical personnel.
•  Read, understand and follow the instructions before installing this product.
•  Turn off all power supplying equipment before working on or inside the equipment.
•  Use a properly rated voltage sensing device to confirm power is off.
  DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION
•  Only install this product on insulated conductors.

Failure to follow these instructions will result in death or serious injury.

DANGER

Wiring ExamplE

H921

921

DimEnsions

NOTICE

•  This product is not intended for life or safety applications.

•  Do not install this product in hazardous or classified locations.

•  The installer is responsible for conformance to all applicable codes.

•  Mount this product inside a suitable fire and electrical enclosure.

Fan or Pump 

CONTROLLER

4-20mA  DC

Analog

Input

MOTOR 

CONTACTOR 

Removable Mounting Bracket

Self-gripping 

Iris

1.0”

(25 mm)

0.8”

(21 mm)

1.1”

(26 mm)

3.1”

(79 mm)

2.8”

(70 mm)

Ø = 0.3”

(8 mm)

1.4” 

(36 mm)

2.5”

(64 mm)

3.0”

(76 mm)

Bracket can be mounted 
on either side for added 
installation flexibility.

Use DIN Rail 

Mounting clip 

(Veris part 

number AH01) to 

mount on stan‑

dard DIN rail.

Quick install

Disconnect and lock out power to the conductor to be monitored. 

1.  

Plan the installation:  

2.  

Locate a mounting surface for the removable mounting bracket that will allow 
the monitored conductor to pass through the iris, or “window” when it is installed 
and keep the product at least 1/2” (13mm) from any uninsulated conductors (CE). 
Determine cable routing for the controller connection, allowing wiring to reach 
the mounting location.

Install mounting bracket  

3.  

Drill holes to mount the bracket to the chosen surface using the included screws.

Set the desired amperage range (30, 60, or 120 Amps).

4.  

Wire the output connections between the sensor and the controller (4-20mA).

5.  

Snap the sensor over the wire to be monitored and clip the assembly to the 

6.  

mounting bracket.

Scale the controller software to match the selected output.