HAUBER-Elektronik GmbH
17
14.2.2
Alternative earthing concept
With the alternative earthing concept, the sensor cable shield is connected to the sensor
housing. The sensor housing is uncoupled from the machine earth by means of an EMC
adapter (red). With the alternative earthing concept, an electrically secure earth connection can
only be ensured for versions with an M12 plug connection. For versions with an integrated
cable, the alternative earthing concept cannot be used.
1
Machine earth
2
Evaluation unit (measuring device, PLC, etc.)
3
Blue
– 4–20 mA current signal
4
Brown
– 10–30 V DC
5
Cable shield
6
Evaluation unit earth potential
7
EMC adapter (Hauber art. no. 10473)
Please advise us if you are opting for the alternative earthing concept when
enquiring. We will offer you the relevant sensor cable and the EMC adapter.