www.microdam.co.kr
Mini Piston Pump Series
USER GUIDE
MERCURY
Silent, Modern, & Reliable
<MERCURY>
Model No. MD1010PM
For Air Conditioning up to 7kW
<MERCURY PLUS>
M DUCTS
Smart Guard for Your Comfortable Place!
Please read this user guide carefully before attempting to install, operate or service
the MICRODAM pump. Know the pump application, limitations and potential hazards.
Protect yourself and others by observing all safety information. Failure to comply
with instructions could result in personal injury and/or property damage. Retain this
user guide for future reference. Installation, connections, and after-sale service are
to be made by a qualified person.
LIMITED WARRANTY
MICRODAM condensate removal pump is warranted against defective materials and workmanship
for a period of 12 months. Any product that should fail for either of the above two reasons and is still
within the warranty period will be repaired or replaced at the option of Sungshin hasco, Ltd. as the sole
remedy of buyer.
For our customers located outside of Korea (R.O.K), please return the defective unit to any authorized
local distributor or dealer with a brief written explanation of the problem. If there are no apparent signs
of customer abuse, unit will be repaired or replaced. If dispute arises over replacement of the pump, the
distributor or dealer is to segregate such items and hold for inspection by a representative of Sungshin
Hosco, Ltd. or notify factory with details of the problem for factory disposition and settlement of warranty
claim.
DISCLAIMER : The foregoing warranty is an exclusive warranty in lieu of any other express warranties.
Any implied warranties (including, but not limited to any implied warranty of merchantability or fitness
for a particular purpose) to the extent either applies to a pump shall be limited in duration to the periods
of the express warranties given above.
Warranty will be VOID if any of the following conditions are found :
1. Sealed motor housing opened.
2. Product connected to voltage other than indicated on nameplate.
3. Cord cut off to a length less than three feet.
4. Pump allowed to operate dry (fluid supply cut off).
5. Pump used to circulate anything other than fresh water at approximately room temperature.
6. Any type of product abuse by customer.
Any oral statements about the product made by the seller, the manufacturer, the representatives or
any other parties, do not constitute warranties, shall not be relied upon by the user and are not part
of the contract for sale. Seller’s and manufacturer’s only obligation, and buyer’s only remedy, shall
be the replacement and/or repair by the manufactruer of the product as described above. Neither seller
nor the manufacturer shall be liable or any injury, loss or damage, direct, incidental or consequential
(including, but not limited to incidental or consequential damages for lost profits, lost sales, injury to
person or property, or any other incidental or consequential loss), arising out of the use or the inability
to use the product and the user agrees that no other remedy shall be available to it. Before using, the
user shall determine the suitability of the product for the intended use, and user assumes all risk and
liability whatsoever in connection therewith. We recommend each pump be used with a GFCI (Ground
Fault Circuit Interrupter).
MADE IN KOREA
(10) Make sure that the power source voltage matches with the pump’s requirement. Connect the power
supply cable(8) to a constant source of power (not a fan or other device that runs intermittently).
Do NOT connect or link the air conditioner’s power cable directly to the power supply cable of pump(8).
(11) When all the above tasks are done, please perform trial operations.
<TIP> TRIAL OPERATION
→
After the installation, please test pump’s operation for 8~10 times by pouring water slowly
into the drain pan of air conditioner.
→
Please check if there is any water leak or siphoning action.
→
There will be clicking noises for the initial start up phase only (usually for the first 1~5 times
of pumping operation) which is not a disorder but a normal operation.
SERVICE & MAINTENANCE INSTRUCTIONS
1) Before attempting to service or disassemble any component, make sure that the unit is disconnected
from the power source.
2) The cleaning of reservoir should be done every six months usually at the beginning and the end of
the air conditioning season.
3) Open the reservoir cover using the opening wing.
4) Clean the reservoir and the float using a solution of water containing 5% bleach. Replace the float
in the initial position (Magnet Faced Up) and reinstall the reservoir cover.
5) Perform the trial operation.
TROUBLESHOOTING
The unit does not run.
The unit makes loud noises
even after the first dry-running
phase.
The unit runs but does not
pump the liquid out properly.
→
Check the power supply.
→
Check the air conditioner to see if the condensation is
actually being produced.
→
Make sure the inlet piping is not clogged.
→
Check if the pump is contacting with any hard surfaces.
If it is, anti-vibration materials should be positioned
betwee the pump and the hard surface.
→
Make sure there is no siphoning action.
→
Check the highest point of the discharge piping does not
exceed the maximum delivery head of the pump.
→
Check every piping is not clogged or twisted.
→
Check the flow rate of the pump is sufficient for the
condensation volume of air conditioner.
"Acceptable For Indoor Use Only"
"Nonsubmersible Pump"
"CAUTION"
- To reduce risk of electric shock, install with motor and all electrical
components above the top grade level of the sump. This pump is not sbmersible.
"WARNING"
"Risk Of Electric Shock - This Pump Has Not Been Investigated For Use In Swimming Pool
Or Marine Areas."
"To reduce risk of electric shock, see instruction manual for proper installation."
"To reduce risk of electric shock, connect only to a properly grounded, grounding-type
receptacle."
"ATTENTION"
- Pour réduire les risques de choc électrique, d'installer avec moteur et
tous les composants électriques au-dessus du sol haut de puisard. Cette pompe n'est pas
submersible.
"AVERTISSEMENT"
"Risque de chocs électriques - Cette pompe n'a pas été étudiée pour une utilisation dans
une piscine ou marine."
"Pour réduire les risques de choc électrique, voir le manuel d'instructions pour une
installation correcte."
"Pour réduire les risques de choc électrique, connecter uniquement à une prise
correctement mise à la terre-type décipient."
"THERMALLY PROTECTED"
Date of Production: it is stamped on the reservoir.
"FOR INDOOR USE ONLY"
“EMPLOYER UNIQUEMENT À L’INTÉRIEUR”
“ENCLOSURE TYPE 2”
“BOÎTIER DE TYPE 2”
PRODUCT LABEL
Tel : +82.53.853.8826, 8827
Fax : +82.53.853.8828
E-mail : [email protected]
www.microdam.co.kr
MICRODAM-12/2014