![HART Proline Promag 55 Скачать руководство пользователя страница 141](http://html1.mh-extra.com/html/hart/proline-promag-55/proline-promag-55_manual_601405141.webp)
Device Functions Proline Promag 55
10 Block SPECIAL FUNCTION
Hauser
141
10.2
Group SOLID CONTENT FLOW
!
Note!
A brief introduction to the calculation of solid content flows with Promag 55 and the requirements
needed for this can be found in the Operating Instructions (BA119D/06/en).
Observe the following points when commissioning the solid content flow function:
1.
Be aware that the settings in the following functions are identical both for the flowmeter and
for the external density meter:
– ASSIGN CURRENT (5200)
– CURRENT SPAN (5201)
– VALUE 0_4 mA (5202)
– VALUE 20 mA (5203)
– ERROR-VALUE (5204)
– UNIT DENSITY (0420)
2.
Enter the following density values:
SPECIAL FUNCTIONS > SOLID CONTENT FLOW > CONFIGURATION >
CARRIER DENSITY (7711) and TARGET MAT. DENSITY (7712)
3.
Enter the desired density unit:
MEASURED VARIABLES > SYSTEM UNITS > ADDITIONAL CONFIGURATION >
UNIT DENSITY (0420)
4.
The "ASSIGN …" functions can also be used to assign the calculated solid content flow
measured variables to a display line or to the outputs (current, frequency, relay).
10.2.1
Function group CONFIGURATION
SPECIAL FUNCTION
H
⇒
SOLID CONTENT FLOW
HFA
⇒
CONFIGURATION
770
Function description
SPECIAL FUNCTION
➞
SOLID CONTENT FLOW
➞
CONFIGURATION
CARRIER DENSITY
(7711)
!
Note!
This function is only available if the measuring device has an F-CHIP for calculating solid
content flows (order option).
In this function, the density of the transporting liquid
(e.g. water) can be entered, in order
to calculate the flow rate of solids. This density value can, for example, be determined
from reference tables or by means of corresponding laboratory tests.
User input:
5-digit floating-point number (0 to 99999), including unit
Factory setting:
1.0 kg/l
Содержание Proline Promag 55
Страница 2: ...Device Functions Proline Promag 55 2 Endress Hauser ...
Страница 5: ...Device Functions Proline Promag 55 Contents Endress Hauser 5 ...
Страница 164: ...14 Index Device Functions Proline Promag 55 164 Endress Hauser ...
Страница 166: ...www endress com worldwide BA120D 06 en 10 09 71104957 FM SGML6 0 ...