Device Functions Proline Promag 55
9 Block BASIC FUNCTION
Hauser
125
9.4
Group SENSOR DATA
9.4.1
Function group CONFIGURATION
BASIC FUNCTION
G
⇒
HART
GAA
⇓
PROCESS PARAMETER
GIA
⇓
SYSTEM PARAMETER
GLA
⇓
SENSOR DATA
GNA
⇒
CONFIGURATION
680
Function description
BASIC FUNCTION
➞
SENSOR DATA
➞
CONFIGURATION
All sensor data (calibration factors, zero (point) and nominal diameter) are set at the factory and saved on the S-DAT
sensor memory chip.
!
Note!
The individual values of the functions are also provided on the sensor nameplate.
"
Caution!
Under normal circumstances you should not change the following parameter settings, because changes affect numerous
functions of the entire measuring facility in general and the accuracy of the measuring system in particular. For this
reason, the functions described below cannot be changed even when you enter your personal code.
Contact the Hauser service organization if you have any questions about these functions.
CALIBRATION DATE
(6808)
Use this function to view the current calibration date and time for the sensor.
User interface:
Calibration date and time
Factory setting:
Calibration date and time of the current calibration.
!
Note!
The calibration date and time format is defined in the FORMAT DATE/TIME (0429)
function,
K-FACTOR
(6801)
Use this function to display the actual calibration factor (positive flow direction) for the
sensor. The calibration factor is determined and set at the factory.
User interface:
5-digit fixed-point number: 0.5000 to 2.0000
Factory setting:
Depends on nominal diameter and calibration
ZERO POINT
(6803)
Use this function to view the actual zero-point correction value for the sensor.
Zero-point correction is determined and set at the factory.
User interface:
max. 4-digit number: –1000 to +1000
Factory setting:
Depends on nominal diameter and calibration
NOMINAL DIAMETER
(6804)
Use this function to view the nominal diameter of the sensor. The nominal diameter
depends on the size of the sensor and is set at the factory.
User interface:
2 to 2000 mm or 1/12 to 78"
Factory setting:
Depends on the size of the sensor
Содержание Proline Promag 55
Страница 2: ...Device Functions Proline Promag 55 2 Endress Hauser ...
Страница 5: ...Device Functions Proline Promag 55 Contents Endress Hauser 5 ...
Страница 164: ...14 Index Device Functions Proline Promag 55 164 Endress Hauser ...
Страница 166: ...www endress com worldwide BA120D 06 en 10 09 71104957 FM SGML6 0 ...