Device Functions Proline Promag 55
8 Block INPUTS
Hauser
105
8.1
Group STATUS INPUT
8.1.1
Function group CONFIGURATION
INPUTS
F
⇒
STATUS INPUT
FAA
⇒
CONFIGURATION
500
Function description
INPUTS
➞
STATUS INPUT
➞
CONFIGURATION
ASSIGN STATUS INPUT
(5000)
Use this function to assign a switching function to the status input.
Options:
OFF
RESET TOTALIZER (1 to 3)
RESET ALL TOTALIZERS
POSITIVE ZERO RETURN
RESET FAULT MESSAGE
Factory setting:
OFF
"
Caution!
Positive zero return is active as long as the level is available at the status input
(continuous signal). All other assignments react to a change in level (pulse) at the status
input.
ACTIVE LEVEL
(5001)
Use this function to define whether the assigned switch function is released or sustained
when the signal level is present (HIGH) or not present (LOW).
Options:
HIGH
LOW
Factory setting:
HIGH
MINIMUM
PULSE WIDTH
(5002)
Use this function to define a minimum pulse width which the input pulse must achieve in
order to trigger the selected switching function (see function ASSIGN STATUS INPUT
(5000)).
User input:
20 to 100 ms
Factory setting:
50 ms
Содержание Proline Promag 55
Страница 2: ...Device Functions Proline Promag 55 2 Endress Hauser ...
Страница 5: ...Device Functions Proline Promag 55 Contents Endress Hauser 5 ...
Страница 164: ...14 Index Device Functions Proline Promag 55 164 Endress Hauser ...
Страница 166: ...www endress com worldwide BA120D 06 en 10 09 71104957 FM SGML6 0 ...