HARTCOM-W2 User Manual
4/2/2018
Designed and Produced under
Page 28 of 71
ISO 9001:2008 Certification
Step
Action
2
Click
Set
to open the Method dialog box (below is an example of a Method dialog box):
3
Click either:
•
OK
to move to the next dialog in the Method sequence.
•
Abort
to cancel the Method execution.
•
Help
to get specific help for that step of the Method. This Help information is provided by
the device DD.
4.4 Calibrating HART Field Devices
Calibration of field devices and loop test are achieved by executing the Methods or Standard Operating Procedures
that are specific to device. Methods are defined based on the test parameters specific to the device, providing
information for the calibration of that device.
See the previous section for Method execution.
4.5 Viewing the Device Status
DevCom2000 provides the user with the ability to monitor the device specific status of the device and the
communication network.
When there is error communicating with the device, it is recognized and indicated to the user. The user can view
more details of such errors, using the
View
→
Device
Condition from the main window.
To view the device and communication status, perform the following steps: