Guidelines 

Water chemistry 

Special attention should be paid to the chemical balance of the pool water. The values 
should always stay within the following limits: 

 

 

Min 

Max 

pH 

7,0 

7,4 

Free chlorine (mg/l) 

0,5 

1,2 

TAC (mg/l) 

80 

120 

Salt (g/l) 

 

 

Attention! 

 

Failure to keep the swimming pool water between above limits will invalidate the 
warranty 

 

When the concentration of one or more products mentioned above becomes too 
high, irrevocable damage to your heat pump may occur.  Make sure that you 
always install water treatment equipment after the heat pump. 

 

When an automatic chemical feeder is installed in the tubing, it must be installed 
downstream of the heat pump. 

 

A check valve must be installed between the heat pump and the chemical feeder to 
prevent back-siphoning of chemically saturated water into the heat pump where it 
will damage the components. 

 

Winter-ready 

Attention! 

Failure to winterize could cause damage to the heat pump and will void warranty. 

In areas where freezing temperatures occur, you should protect your pump, filter and heat 
pump from the elements. Perform the following steps to completely drain the heat pump. 

 

1.  Turn off the electrical power to the heat pump at the main breaker panel. 
2.  Shut off the water supply to the heat pump: close valves 2 and 3 on the by-pass completely. 
3.  Disconnect the water inlet and outlet and let the water drain from the heat pump. Blow 
all water out of the heat pump. 
4.  Re-connect the water inlet and outlet loosely to prevent debris entering the connections. 
 

 

Содержание Harmo Kubi ZVWX4015

Страница 1: ...Imported by Zwembad BVBA Industrieweg 9 3190 Boortmeerbeek Belgi www harmopool eu Swimming pool heat pump Harmo Kubi Model ZVWX4015 ZVWX5010 ZVWX5020 ZVWX5030 Instruction manual...

Страница 2: ...7 Configuration 8 Installation of the bypass 9 Electrical wiring 10 Start up procedure 11 Daily use of the heat pump 11 Condensation 11 Guidelines 12 Water chemistry 12 Winter ready 12 Spring start up...

Страница 3: ...comply with these recommendations will void warranty The swimming pool heat pump unit heats the swimming pool water and keeps the temperature constant Characteristics Durable the heating exchanger is...

Страница 4: ...Controller Digital control Condenser Titanium heat exchanger Compressor Quantity 1 1 1 1 Compressor Rotary Rotary Rotary Rotary Refrigerant R410a R32 R410a R32 R410a R32 R410a R32 Weight refrigerant 7...

Страница 5: ...5 Dimensions of the heat pump Model Size mm ZVWX5010 ZVWX5020 ZVWX5030 A 670 G 101 F 250 ZVWX4015...

Страница 6: ...ways keep the unit straight up If the unit has been tilted or put on his side allow 24h before starting the unit Location The unit may be installed virtually anywhere outdoors For indoor pools please...

Страница 7: ...er 30 meters could roughly be estimated at 0 6kw hour 2000 BTU for every 5 temperature difference between the pool water and the soil surrounding the pipe which translates to an operation time increas...

Страница 8: ...8 Configuration Note the above piping connection is only an example for demonstration...

Страница 9: ...set correctly your heat pump will deliver its best performance The bypass has to be built as shown below Install the bypass with all 3 valves entirely open Slightly close valve 1 Close valve 3 about...

Страница 10: ...eat pump All heat pumps require a single phase connection Grounding the heat pump is required to protect you against electrical shocks caused by an eventual short circuit inside the heat pump The heat...

Страница 11: ...the unit and that is switched off when the water flow becomes too low e g when the filter pump is switched of Time Delay the unit is equipped with a built in 3 minute start delay to protect electrical...

Страница 12: ...pump A check valve must be installed between the heat pump and the chemical feeder to prevent back siphoning of chemically saturated water into the heat pump where it will damage the components Winte...

Страница 13: ...pouring down onto the unit 6 Do not use the heat pump if any part has been under water Immediately call a qualified professional technician to inspect the heat pump and replace any part of the contro...

Страница 14: ...setting Press to alter Press SET again to confirm Press M again 9 0 Press SET to enter water pump setting Press to alter Press SET again to confirm Press M again A 40 Press SET to enter return water t...

Страница 15: ...ter from 00 G see the Operation Parameter Table o Under parameter setting press or to set data o Please note no motion on the display for 10s the LCD will display water in water out temp under running...

Страница 16: ...s M for 5 seconds to check the current status of the unit You can check water in water out temp condenser temp and ambient temp Please note no motion on the display for 10s The LCD will display water...

Страница 17: ...technicians 06 Electronic expansion valve mode 0 Manuel 1 AUTO 1 Adjusted by technicians 07 Automatic restarting after power off 0 1 1 record Adjusted by technicians 08 Mode cooling only heat pump aux...

Страница 18: ...he unit as a result of the dirty or clogged filter o The area around the unit should be dry clean and well ventilated Clean the side heating exchanger regularly to maintain good heat exchange and to s...

Страница 19: ...etc Consult your dealer If the power supply cord is damaged it must be replaced by the manufacturer or its service agent in order to avoid a hazard When installing relocating or servicing the unit ma...

Страница 20: ...e The appliance shall be stored in a room without continuously operating ignition sources for example open flames an operating gas appliance or an operating electric heater Be aware that refrigerants...

Страница 21: ...her electric appliances or furniture under the heat pump unit Water may drip down from the unit which may cause damage or malfunction o Do not leave the unit on a damaged installation stand the unit m...

Страница 22: ...lower vase on it this may cause fire or electric shock o Do not step on or place any object on the unit this may cause injury if you or the object falls down o Dirty filters cause condensation in the...

Страница 23: ...p before you do maintenance R32 Leak detector Explosion proof vacuum pump Anti static gloves IMPORTANT On the heat pump you find the ref of the gas used This is the R410 gas or R32 If your heat pump c...

Страница 24: ...time freezing protection in winter PP 07 Ambient temp too low The second time freezing protection in winter PP 07 Ambient temp too low Coil sensor failure cooling mode PP 08 The sensor is open or sho...

Страница 25: ...25 Wiring diagram Model ZVWX5010 ZVWX5020 ZVWX5030...

Страница 26: ...26 Warranty...

Отзывы: