Network Configuration
47
•
•
•
•
•
•
Select Save Parameter to save the entry.
Click Home to return to the home page.
On the
HI 6500 series instrument display
, select the communication menu and use
the UP or DOWN button to select the Modbus-RTU submenu, then select the Slave
Address menu item. The current Termination value will be displayed, press the
ENTER or the RIGHT button to change the parameter if the Termination needs to be
modified.
Modbus-RTU (over RS-485
)
Step 1. Setup a slave address assigned to the HI 6500 series instrument from the
communications menu and the Modbus-RTU submenu.. Use a unique address
between 1 and 247
Step 2. Set the Baud Rate to the same as the master device, typically 9600 or 19,200
Step 3. Set the Parity Bit parameter to match that of the Modbus-RTU master (EVEN,
ODD, or OFF)
The RS 485 half duplex pinout is:
Modbus Setup
•
Slave Address
may be set to any number in the range of 1-247.
•
Set
Baud
Rate
parameter to match the settings of the Modbus master
•
Set
Parity
to match the settings of the Modbus master
Modbus Functions
The Modbus functions allowed in the HI 6500 are:
Function 3: Modbus Read Holding Registers
Function 4: Modbus Read Input Registers
Function 6: Modbus Write Single Register
Function 16 (0x10): Modbus Write Multiple Registers.
Modbus Registers
This instrument has 64 16-bit MODBUS input registers and 64 16-bit output registers. The
data in these registers is in "big endian" format, meaning that the most significant byte
comes first.
•
The first 6 registers (0 – 5) are used for the “command interface” in the unit.
•
Registers 6 & 7 will contain the Net weight in 32 bit floating point format.
•
Registers 8 & 9 will contain the Gross weight in 32 bit floating point format.
GND
DNC
TR+
TR-
PrtRX
PrtTX
Signal
Ground
DO Not
Connect
TX+ & Rx- RX+
RS-232
Pins not
Printer
used
Содержание HI 6500 Series
Страница 10: ...viii Contents ...
Страница 20: ...10 Chapter 2 ...
Страница 72: ...62 Chapter 4 ...
Страница 96: ...86 Chapter 5 Profibus DP Commands and Parameters ...
Страница 97: ...Instrument Configuration 87 Serial Option Termination ...
Страница 126: ...116 Chapter 5 ...
Страница 156: ...146 Chapter 8 ...
Страница 163: ...Troubleshooting 153 General Troubleshooting Flow Chart Index ...
Страница 164: ...154 Chapter 9 A Guideline Instability Electrical and Mechanical review ...
Страница 165: ...Troubleshooting 155 A1 Checking for Unstable Components in a Weighing System ...
Страница 166: ...156 Chapter 9 B Guidelines for Electrical Mechanical or Configuration Issues ...
Страница 167: ...Troubleshooting 157 B1 Guidelines to Verify Electrical Installation ...
Страница 168: ...158 Chapter 9 B2 Guidelines to Verify Mechanical Installation ...
Страница 169: ...Troubleshooting 159 B3 Guidelines to Verify Configuration Filter Settings to Improve Stability ...
Страница 170: ...160 Chapter 9 C Integrated Technician and Stability Test Overview ...
Страница 171: ...Troubleshooting 161 E Testing for Non Return to Zero System with IT Summing Card ...
Страница 173: ...Troubleshooting 163 G Calibration Errors When Performing the Calibration ...
Страница 174: ...164 Chapter 9 H Mechanical Installation ...
Страница 175: ...Troubleshooting 165 J Electrical Inspection ...
Страница 176: ...166 Chapter 9 K Installation Check Points ...
Страница 177: ...Troubleshooting 167 M Weight Processor s Front Display is Blank or Locked ...
Страница 178: ...168 Chapter 9 N Analog Out HI 6510 Only ...
Страница 194: ...184 Appendix A Figure D1 Assembling the Swivel Mount Enclosure on the instrument pedestal ...
Страница 195: ...Installation of Swivel Mount Enclosures 185 Figure D2 Assembling the Swivel Mount Enclosure on a Table ...
Страница 196: ...186 Appendix A Dimensions ...
Страница 200: ...4 HI 6500 Series USER GUIDE Index ...
Страница 201: ......