TECHNICAL NOTE 

 
 

Setup and Test the Analog Output on the HI 4050 unit 

 

The purpose of this technical note is to guide the user through the setup, testing and 
calibration, if necessary, of the Analog output option on the HI 4050 unit. 
This setup can be performed either through the front keypad or the online browser.  These 
instructions will not differentiate between the two methods. 
 
The analog output option on the HI 4050 unit has four channels.  The first and third 
channels are a voltage output and the second and fourth channels are current output. 
Each channel is independent from the other channels. 
 

Setup: 

 
OUTPUTS: 
 

Default outputs are: 
Channel 1: 0-10 V 
Channel 2: 4-20 mA 
Channel 3:  0-10 V 
Channel 4:  4-20 mA 
Each of the analog output channels allows the user to change the output range of the 
channel.  So the channels can be changed to be anywhere from x to y, where x is the low 
output (range 0-10 V or 0-20 mA) and y is the high output (range 0-10 V or 0-20 mA). 
Examples: 
Channel 1: 0-5 V; 
Channel 2: 0-20 mA; 
Channel 3: 10-0 V; (note the reverse output levels.) 
Channel 4: 4-12 mA;  
 

INPUTS: 

 
Default inputs are: 0-100 for all channels. 