SETPOINT MENU
RATE REMOTE
AMOUNT 1 5.000LB
Chapter 8 - Operation
8-15
FIG. 8-18 SELECTING THE REMOTE MODE OF OPERATION
•
The operator can still select the batch amount or continuous opera-
tion from the controller's front panel. The desired Flow Rate is set
by the Remote Set Point Input Option Card.
•
The operation of the HI 2160RC
PLUS
is controlled by the Host.
Setting the
Automatic Rate
Control Mode
(Gravimetric Mode)
•
The Automatic Rate Control Mode is used if the operator wants to
set a rate of flow to a pre-determined rate.
•
The rate is set in mass units/time units. For example LBS/M
(pounds per minute), LBS/H (pounds per hour) etc.
Step 1. Press on the Set Pt button.
Step 2. Enter the security code number.
Step 3. Press on the Enter button. The Set Point Menu appears with
the cursor to the left of the RATE sub-menu. (See Fig. 8-18)
Step 4. If the Rate display shows "MANUAL" or "REMOTE", press
on the Select button to select the Value display. (See Fig. 8-
19)
Содержание HI 2160RC PLUS
Страница 1: ...HI 2160RCPLUS Rate Controller Operation and Installation Manual ...
Страница 23: ...HI 2160RCPLUS MANUAL 2 6 ...
Страница 32: ...Chapter 3 Installation 3 9 FIG 3 12 FRONT PANEL WITH BRACKETS FROM FACTORY FIG 3 13 BEZEL INSTALLATION DIAGRAM ...
Страница 46: ...Chapter 3 Installation 3 23 Interconnect Wiring Diagram See Fig 3 33 FIG 3 33 INTERCONNECT WIRING DIAGRAM ...
Страница 48: ...Chapter 3 Installation 3 25 FIG 3 35 SECURE MEMORY MODULE FIG 3 36 INSTALLING REMOVING SECURE MEMORY MODULE ...
Страница 49: ...HI 2160RCPLUS MANUAL 3 26 ...
Страница 67: ...HI 2160RCPLUS MANUAL 4 18 ...
Страница 91: ...HI 2160RCPLUS MANUAL 5 24 ...
Страница 151: ...HI 2160RCPLUS MANUAL 7 12 ...
Страница 187: ...HI 2160RCPLUS MANUAL 8 36 ...
Страница 197: ...1 2 3 4 5 6 V V I I VOLTAGE CURRENT HI 2160RCPLUS MANUAL 9 10 FIG 9 5 CONNECTOR WIRING DIAGRAM FOR CONTROL OUTPUT CARD ...
Страница 207: ...HI 2160RCPLUS MANUAL 9 20 ...
Страница 219: ...Data Worksheets WKSHT 6 ...