TUNING/CONTROL MENU
CTL. OUT LO (%)
CTL. OUT HI (%)
AVRG. (1 -200)
26
74
200
Chapter 6 - Setup
6-45
FIG. 6-39 TUNING/CONTROL MENU/SETTING CONTROL OUT HI
PERCENTAGE/74
Step 20. Press the Enter button to accept the new value.
Step 21. The operator cannot set a flow rate higher than 74% of full
span which equates to 11.6 lbs/m in our example. If a flow
rate is entered higher than 11.6 lbs/m an error statement
appears “SETTING TOO HIGH”.
Step 22. Press the Exit button to return to the Main Menu.
Step 23. Press the Exit button to return to the Operating Display.
Setting Up the Analog
Output Option
•
The Analog Output Option contains user-scaled calibration data
used to transmit information to a PLC, recorder, remote display, or
similar devices accepting analog input signals.
Step 1. From the Main Menu press the down arrow
↓
button until the
cursor is to the left of the Analog Output Sub-Menu. (See Fig.
6-40)
Содержание HI 2160RC PLUS
Страница 1: ...HI 2160RCPLUS Rate Controller Operation and Installation Manual ...
Страница 23: ...HI 2160RCPLUS MANUAL 2 6 ...
Страница 32: ...Chapter 3 Installation 3 9 FIG 3 12 FRONT PANEL WITH BRACKETS FROM FACTORY FIG 3 13 BEZEL INSTALLATION DIAGRAM ...
Страница 46: ...Chapter 3 Installation 3 23 Interconnect Wiring Diagram See Fig 3 33 FIG 3 33 INTERCONNECT WIRING DIAGRAM ...
Страница 48: ...Chapter 3 Installation 3 25 FIG 3 35 SECURE MEMORY MODULE FIG 3 36 INSTALLING REMOVING SECURE MEMORY MODULE ...
Страница 49: ...HI 2160RCPLUS MANUAL 3 26 ...
Страница 67: ...HI 2160RCPLUS MANUAL 4 18 ...
Страница 91: ...HI 2160RCPLUS MANUAL 5 24 ...
Страница 151: ...HI 2160RCPLUS MANUAL 7 12 ...
Страница 187: ...HI 2160RCPLUS MANUAL 8 36 ...
Страница 197: ...1 2 3 4 5 6 V V I I VOLTAGE CURRENT HI 2160RCPLUS MANUAL 9 10 FIG 9 5 CONNECTOR WIRING DIAGRAM FOR CONTROL OUTPUT CARD ...
Страница 207: ...HI 2160RCPLUS MANUAL 9 20 ...
Страница 219: ...Data Worksheets WKSHT 6 ...