Series B 

HI 1746-WS 

 

The Button 

J2

 

Pin |  Signal

 

16     Aux In 
15     N.C 
14     GND 
13     +V 
12     Relay 2 
11     +V 
10     Relay 1 
9       C2- 
8       C2+ 
7       -Exc 
6       -Sen 
5       -Sig 
4       +Sig 
3       +Sen 
2       +Exc 
1       Shield

 

FAULT 

COMM 

C2 

WEIGH SCALE 

LEDS 
Run/Fault LED 

Flashing 

Green

 Self-Test is running. 

Flashing 

Green

, (5Hz Flash Speed) - Self-Test Failed, or 

calibration has not been completed correctly. 
Steady 

Green

 Self-Test Passed 

Flashing 

Red 

Weigh Scale Module has a fault. 

 

(The load cell Millivolt signal level is out of range.) 

Steady Red Module has a major problem.  

 

Contact Hardy 

Instruments Customer Support for assistance.

 

Comm. LED  

Flashing 

Green

, Block transfer is being performed. 

(Normal Operation) 
LED is Off, No Communication, check I/O configuration. 
 

C2 LED  

Steady 

Green

, C2 load cell(s) has been found. 

LED is Off, No C2 load cells have been found. 
Steady 

Red

, Unable to read load cell data or the Load cell 

data is in error.

 

What do I check first? 

 

Are the COMM and FAULT led green?   

o

 

See led section above:  

o

 

IF NO see reverse page 

o

 

C2 led is dependent on, if the load cells are C2 enabled.  (See led section above.) 

 

Does the weight change increase as weight is applied? 

o

 

Monitor the PLC screen to verify: 

 

Simply apply weight to the scale 

 

Does it return to the original weight reading or drift about and then 
return to zero? 

 

Is the weight correct? 

 

Is the weight stable to 1:10,000? 

 

Is the weight correct at multiple weighing stages? 

 

Verify the load cell signal output  

 

C2+ = gray, C2- = Violet, voltage 4.9vdc 
Excitation = 5vdc 
Signal range is –0.1mvdc to 15.3mvdc  
Sense lines installed to the junction box or jumpers. 
Shields landed to make this the single ground point 

HI 1746WS System troubleshooting Quick Reference Guide 