HI 1756-WS WEIGH SCALE MODULE
4-18
Return Data:
• COMMAND
• CHANNEL
• STATUS
• 9 DINT SERIAL NUMBER
Error Return Values:
• OUTOFTOLERANCE - No C2 Sensor found.
Read Status of
Module
(GETSTATUS)
Reads the condition of the module.
Command Number: 0x80 (Hexadecimal)
Channel Number: 0 or 1
Number of Elements: 8
NOTE:
See the Timed Out Command section.
Return Data:
• COMMAND
• CHANNEL
• STATUS - Returns status of the last timed out
command.
Write Parameters
(WRITEPARAM)
Writes all the parameters.
Command Number: 0x68 (Hexadecimal)
Channel Number: 0 or 1
Number of Elements: 84
Return Data:
• COMMAND
• CHANNEL
• STATUS - The status is 0 if the command suc-
ceeded. If there was a range error detected in one
of the parameters, a non-zero value is returned
indicating which parameter failed its range. (See
Table 4-1)