Chapter 4 - Setup
4-7
FIG. 4-4 DISCRETE DATA
STATUSWORD bit positions refer to these variables:
Word
Number
Definition
ERRORADCONVERT
0x0001
Millivolt return from the load cell
system is out of range for the unit.
ERRORADFAILURE
0x0002
A/D converter in the unit is no
longer responding.
STATUSENGLISH
0x0004
Unit calibrated in lbs. If the bit is
off, calibrated in kgs.
STATUSZTRACK
0x0008
Auto Zero Tracking is turned on.
STATUSBUTTONENABLED
0x0010
Enabled/Disabled calibrate button.
STATUSINMOTION
0x0040
Weight is changing on the scale.
ERRORNOCAL
0x0080
The unit is at factory default set-
tings.
ERROREEPROMWRITE
0x0100
EEPROM Hardware Error
ERROREXCITEMON
0x0200
Excitation monitor error.
ERRORMAX144
0x0400
Hardware Error in Excitation
Monitor
STATUSCMDRCVD
0x2000
Output Table Command Complete