Ex db 

Protection of devices against ignition of dust by means of a "t" housing. 

Explosives group 

IIC 

The device can be used in the presence of explosion hazard of gases, 
vapours and mists of flammable liquids with air classified as explosion 
group IIA, IIB or IIC. 

IIIC 

The device can be used in the presence of explosion hazard of 
flammable dust and fibres belonging to the explosion groups IIIA, IIIB and 
IIIC (all types of dust). 

Temperature class 

T4 

The device is designed for use in hazardous areas of gases with a self-
ignition temperature of > 135°C. 

Temperature 

70°C 

The device can be used in the presence of dust whose cloud auto-ignition 
temperature is higher than 105

°C and the smouldering temperature of the 

layer (5mm) is higher than 145

°C. 

Explosion protection level 

Gc 

Equipment intended for installation in gas explosion hazard Zone 2 which 
provides a 'normal level of safety' and which will not become a source of 
ignition under normal conditions of use and during expected failure. 

Db 

Equipment intended for installation in dust explosion hazards 21, 22 
which provides a "high level of safety" and which will not become a 
source of ignition under normal conditions of use and during expected 
damage. 

 

3. 

SAFETY 

3.1 General precautions 

 

 

DANGER: 

THE EXPLOSION HAZARD CAUSED BY IMPROPER USE AND/OR ALTERATIONS 

TO THE DEVICE CAN CAUSE SERIOUS OR FATAL INJURIES.

  

 

 

WARNING: 

FAILURE TO COMPLY WITH THE REQUIREMENTS OF THIS MANUAL MAY VOID 

THE MANUFACTURER'S WARRANTY. 

 

 

WARNING: 

FAILURE TO COMPLY WITH THE INSTALLATION AND USE RULES MAY RESULT 

IN PERSONAL INJURY OR PROPERTY LOSS. THE MANUFACTURER IS NOT RESPONSIBLE 
IN SUCH CASES. 

 

 

 
 

 
 
 
 
 
 

 

Luminaires must be installed and maintained in accordance with the requirements of this manual and in accordance 
with EN/IEC 60079-14 (current edition). 
 
The Buyer and/or the End User must be aware of the hazards of the electrical, chemical and physical properties of gas, 
vapours and dust present in the installation. Proper installation and maintenance in accordance with local and national 
regulations, product specifications are the responsibility of the Buyer and/or the End User. 
It is not allowed to use a partially damaged device. 
 

 

 
WARNING: 

MAKING ANY MODIFICATIONS TO THE DEVICE IS PROHIBITED.

 

 

WARNING: 

BEFORE  PERFORMING  ANY  ASSEMBLY  OPERATIONS,  INCLUDING  OPENING 

THE CASE, IT IS IMPERATIVE THAT THE DEVICE BE DISCONNECTED FROM THE POWER 
SOURCE.

 

Содержание OptiLine A1 Series

Страница 1: ...1 z 16 USE AND MAINTENANCE INSTRUCTION OF LIGHTING FIXTURE OptiLine A1 SERIES Instruction no K 26190 PW 0006 HARDO Czapski i Wsp lnicy Sp j Release date 04 04 2024 ul Spacerowa 5 Issue no 1 3 32 083...

Страница 2: ...n 7 5 2 Installation 8 5 3 Electrical connection 10 5 3 1 General requirements 10 5 3 2 Execution of luminaire electrical connections 10 6 WORK IN EMERGENCY MODE 11 6 1 General information 11 6 2 Batt...

Страница 3: ...ements of the IECEx system Detailed guidance on potentially explosive atmospheres is given in this document Luminaires are approved for use in both external and internal installations The external hou...

Страница 4: ...50Hz In emergency mode they are powered from a built in Ni Cd battery pack ensuring backup in emergency mode of not less than 1 5 hours A detailed description of the possible configurations and their...

Страница 5: ...log card of the OptiLine lighting fixture 2 2 Ex marking Depending on the version OptiLine series luminaires are marked with Ex features as follow II 3G Ex ec IIC T4 Gc II 2D Ex tb IIIC T70 C Db The i...

Страница 6: ...s a high level of safety and which will not become a source of ignition under normal conditions of use and during expected damage 3 SAFETY 3 1 General precautions DANGER THE EXPLOSION HAZARD CAUSED BY...

Страница 7: ...t temperature range is unacceptable and will lead to faster wear and or damage At the same time it causes the loss of the manufacturer s warranty Note The use of a luminaire outside the designated ran...

Страница 8: ...the GRP lower body At the place where the nuts are mounted the mounting brackets must be fixed with M8 15 mm bolts and M8 spring washers M8 screws should be tightened with a torque of 9 10 Nm Install...

Страница 9: ...Strona 9 z 16 Figure 3 Acceptable mounting position...

Страница 10: ...5 4 mm2 for luminaires powered on one side Single core cross section 2 5 4 mm2 for pass through or crossed powered luminaires Outer diameter of the cable 8 17 mm the value depends on the size and type...

Страница 11: ...ts for emergency lighting OptiLine luminaires A1 have implemented Built in automatic functional test execution Functional tests last one minute and are performed first 1 hour after the first start nex...

Страница 12: ...the capacitance test performed at least once every 52 weeks WARNING ALL REPAIRS INCLUDING REPLACEMENT OF THE LIGHT SOURCE OR BATTERY PACK CAN ONLY BE CARRIED OUT USING ORIGINAL SPARE PARTS AND ONLY BY...

Страница 13: ...At least once every 1 months a visual and close inspection of the lighting fixture should be carried out During the visual inspection luminaires do not need to be disconnected from the power source Th...

Страница 14: ...OSIVE ATMOSPHERE In accordance with the requirements of local regulations electrical tests related to Measurement of the current consumed by the luminaire Measurement of the condition of the insulatio...

Страница 15: ...2 2 Photometric data Photometric data for OptiLine A1 for an ambient temperature of 25 C a bar temperature of 4000K and a colour rendering index CRI 80 are shown in Table 3 Type Luminous flux with AC...

Страница 16: ...dimensions of OptiLine luminaires are shown in Figure 5 and Table 5 Figure 5 Basic dimensions of OptiLine luminaires Type L L1 B H OptiLine 60 670 400 173 107 OptiLine 12 1276 800 173 107 Table 5 Bas...

Отзывы: