Hardo OptiLine A1 Series Скачать руководство пользователя страница 14

 

 
 

Strona 

14

 z 

16

 

 

 

The scope of the detailed inspection should include: 
 

 

Scope of activities for visual and close inspection; 

 

Checking the condition of protective coatings of internal elements of the lighting fixture; 

 

Checking the condition of internal components, e.g.: cable connections, cable connectors, power supply, 
LED modules, cable glands; 

 

Verification of the installation site in terms of possible environmental changes, e.g.: type of hazardous area, 
temperature class, surface temperature, tightness class. 
 

All  irregularities  identified  shall  be  remedied.  A  detailed  description  and  scope  of  activities  is  included  in  the                      
PN-EN/IEC 60079-17:2014-05 standard. 

 

8.3 Additional requirements 

 

 

DANGER: 

EXPLOSION HAZARD. THE FOLLOWING MEASUREMENTS SHALL BE TAKEN IN 

THE ABSENCE OF AN EXPLOSIVE ATMOSPHERE 

 

 
In accordance with the requirements of local regulations, electrical tests related to: 
 

 

Measurement of the current consumed by the luminaire; 

 

Measurement of the condition of the insulation; 

 

Measurement of the effectiveness of the protective connection 

 

9. 

REPAIRS 

 

 

WARNING: 

THE  USE  OF  A  DAMAGED  DEVICE  IS  PROHIBITED  AS  IT  MAY  LEAD  TO 

PERSONAL  INJURY  OR  PROPERTY  LOSS.  THE  MANUFACTURER  DOES  NOT  BEAR  ANY 
LIABILITY IN SUCH CASES

.  

 

 

WARNING: 

ALL  REPAIRS,  INCLUDING  REPLACEMENT  OF  THE  LIGHT  SOURCE  OR 

BATTERY PACK, CAN ONLY BE CARRIED OUT USING ORIGINAL SPARE PARTS AND ONLY 
BY THE MANUFACTURER OF THE LUMINAIRE OR AN AUTHORIZED SERVICE. 

 

10. 

DISPOSAL 

 

 

A symbol placed on the product or on the packaging indicates that the product should 
not be considered normal household waste but must be recycled for electrical and 
electronic equipment. 

 

11. 

WARRANTY CONDITIONS 

 

To read the warranty conditions, please refer to our General Terms and Conditions available at 

www.hardo.tech

.

  

 

 

Содержание OptiLine A1 Series

Страница 1: ...1 z 16 USE AND MAINTENANCE INSTRUCTION OF LIGHTING FIXTURE OptiLine A1 SERIES Instruction no K 26190 PW 0006 HARDO Czapski i Wsp lnicy Sp j Release date 04 04 2024 ul Spacerowa 5 Issue no 1 3 32 083...

Страница 2: ...n 7 5 2 Installation 8 5 3 Electrical connection 10 5 3 1 General requirements 10 5 3 2 Execution of luminaire electrical connections 10 6 WORK IN EMERGENCY MODE 11 6 1 General information 11 6 2 Batt...

Страница 3: ...ements of the IECEx system Detailed guidance on potentially explosive atmospheres is given in this document Luminaires are approved for use in both external and internal installations The external hou...

Страница 4: ...50Hz In emergency mode they are powered from a built in Ni Cd battery pack ensuring backup in emergency mode of not less than 1 5 hours A detailed description of the possible configurations and their...

Страница 5: ...log card of the OptiLine lighting fixture 2 2 Ex marking Depending on the version OptiLine series luminaires are marked with Ex features as follow II 3G Ex ec IIC T4 Gc II 2D Ex tb IIIC T70 C Db The i...

Страница 6: ...s a high level of safety and which will not become a source of ignition under normal conditions of use and during expected damage 3 SAFETY 3 1 General precautions DANGER THE EXPLOSION HAZARD CAUSED BY...

Страница 7: ...t temperature range is unacceptable and will lead to faster wear and or damage At the same time it causes the loss of the manufacturer s warranty Note The use of a luminaire outside the designated ran...

Страница 8: ...the GRP lower body At the place where the nuts are mounted the mounting brackets must be fixed with M8 15 mm bolts and M8 spring washers M8 screws should be tightened with a torque of 9 10 Nm Install...

Страница 9: ...Strona 9 z 16 Figure 3 Acceptable mounting position...

Страница 10: ...5 4 mm2 for luminaires powered on one side Single core cross section 2 5 4 mm2 for pass through or crossed powered luminaires Outer diameter of the cable 8 17 mm the value depends on the size and type...

Страница 11: ...ts for emergency lighting OptiLine luminaires A1 have implemented Built in automatic functional test execution Functional tests last one minute and are performed first 1 hour after the first start nex...

Страница 12: ...the capacitance test performed at least once every 52 weeks WARNING ALL REPAIRS INCLUDING REPLACEMENT OF THE LIGHT SOURCE OR BATTERY PACK CAN ONLY BE CARRIED OUT USING ORIGINAL SPARE PARTS AND ONLY BY...

Страница 13: ...At least once every 1 months a visual and close inspection of the lighting fixture should be carried out During the visual inspection luminaires do not need to be disconnected from the power source Th...

Страница 14: ...OSIVE ATMOSPHERE In accordance with the requirements of local regulations electrical tests related to Measurement of the current consumed by the luminaire Measurement of the condition of the insulatio...

Страница 15: ...2 2 Photometric data Photometric data for OptiLine A1 for an ambient temperature of 25 C a bar temperature of 4000K and a colour rendering index CRI 80 are shown in Table 3 Type Luminous flux with AC...

Страница 16: ...dimensions of OptiLine luminaires are shown in Figure 5 and Table 5 Figure 5 Basic dimensions of OptiLine luminaires Type L L1 B H OptiLine 60 670 400 173 107 OptiLine 12 1276 800 173 107 Table 5 Bas...

Отзывы: