For the time of storage and transport, the battery packs are disconnected from the power supply. During the connection
operations carried out in accordance with paragraph 5, the battery shall be connected to the terminals of the power
supply according to Figure 4.
After connecting the batteries and supplying mains voltage, the luminaire will go into the charging state, which cannot
be shorter than 24 hours.
Figure 4. Connecting a battery pack
NOTE: Batteries should be replaced at least 4 years from the date of installation, or when the luminaire fails to
maintain its rated operating time after an appropriate charging period, or when the luminaire fails the
capacitance test performed at least once every 52 weeks.
WARNING:
ALL REPAIRS, INCLUDING REPLACEMENT OF THE LIGHT SOURCE OR
BATTERY PACK, CAN ONLY BE CARRIED OUT USING ORIGINAL SPARE PARTS AND ONLY
BY THE MANUFACTURER OF THE LUMINAIRE OR AN AUTHORIZED SERVICE.
WARNING:
WITH THE BATTERY CONNECTED, OPENING THE LIGHTING FIXTURE IS ONLY
POSSIBLE AFTER THE BATTERY HAS BEEN DISCHARGED.
6.3 Status indication
OptiLine **-*******A1- series have a signalling diode mounted on the upper frame (reflector), determining the operating
status of the luminaire. Possible states of signalling diodes are shown in Table 2.
Priority
Description
Status of the
indicator diode
Actions
01
Functional test or capacity in progress
-----
02
LED module damage (short circuit, broken
circuit)
LED module(s) replacement
03
Damage to the battery pack (capacity, voltage)
Battery pack replecement
04
Emergency mode disabled
-----