USE AND MAINTENANCE INSTRUCTION OF
LIGHTING FIXTURE
OptiLine **-*******A1-
SERIES
Instruction no:
K-26190-PW-0006
HARDO Czapski i
Wspólnicy Sp. j.
Release date:
04.04.2024
ul. Spacerowa 5
Issue no:
1.3
32-083 Balice
Страница 1: ...1 z 16 USE AND MAINTENANCE INSTRUCTION OF LIGHTING FIXTURE OptiLine A1 SERIES Instruction no K 26190 PW 0006 HARDO Czapski i Wsp lnicy Sp j Release date 04 04 2024 ul Spacerowa 5 Issue no 1 3 32 083...
Страница 2: ...n 7 5 2 Installation 8 5 3 Electrical connection 10 5 3 1 General requirements 10 5 3 2 Execution of luminaire electrical connections 10 6 WORK IN EMERGENCY MODE 11 6 1 General information 11 6 2 Batt...
Страница 3: ...ements of the IECEx system Detailed guidance on potentially explosive atmospheres is given in this document Luminaires are approved for use in both external and internal installations The external hou...
Страница 4: ...50Hz In emergency mode they are powered from a built in Ni Cd battery pack ensuring backup in emergency mode of not less than 1 5 hours A detailed description of the possible configurations and their...
Страница 5: ...log card of the OptiLine lighting fixture 2 2 Ex marking Depending on the version OptiLine series luminaires are marked with Ex features as follow II 3G Ex ec IIC T4 Gc II 2D Ex tb IIIC T70 C Db The i...
Страница 6: ...s a high level of safety and which will not become a source of ignition under normal conditions of use and during expected damage 3 SAFETY 3 1 General precautions DANGER THE EXPLOSION HAZARD CAUSED BY...
Страница 7: ...t temperature range is unacceptable and will lead to faster wear and or damage At the same time it causes the loss of the manufacturer s warranty Note The use of a luminaire outside the designated ran...
Страница 8: ...the GRP lower body At the place where the nuts are mounted the mounting brackets must be fixed with M8 15 mm bolts and M8 spring washers M8 screws should be tightened with a torque of 9 10 Nm Install...
Страница 9: ...Strona 9 z 16 Figure 3 Acceptable mounting position...
Страница 10: ...5 4 mm2 for luminaires powered on one side Single core cross section 2 5 4 mm2 for pass through or crossed powered luminaires Outer diameter of the cable 8 17 mm the value depends on the size and type...
Страница 11: ...ts for emergency lighting OptiLine luminaires A1 have implemented Built in automatic functional test execution Functional tests last one minute and are performed first 1 hour after the first start nex...
Страница 12: ...the capacitance test performed at least once every 52 weeks WARNING ALL REPAIRS INCLUDING REPLACEMENT OF THE LIGHT SOURCE OR BATTERY PACK CAN ONLY BE CARRIED OUT USING ORIGINAL SPARE PARTS AND ONLY BY...
Страница 13: ...At least once every 1 months a visual and close inspection of the lighting fixture should be carried out During the visual inspection luminaires do not need to be disconnected from the power source Th...
Страница 14: ...OSIVE ATMOSPHERE In accordance with the requirements of local regulations electrical tests related to Measurement of the current consumed by the luminaire Measurement of the condition of the insulatio...
Страница 15: ...2 2 Photometric data Photometric data for OptiLine A1 for an ambient temperature of 25 C a bar temperature of 4000K and a colour rendering index CRI 80 are shown in Table 3 Type Luminous flux with AC...
Страница 16: ...dimensions of OptiLine luminaires are shown in Figure 5 and Table 5 Figure 5 Basic dimensions of OptiLine luminaires Type L L1 B H OptiLine 60 670 400 173 107 OptiLine 12 1276 800 173 107 Table 5 Bas...