HANYOUNG NUX FS - 3 Скачать руководство пользователя страница 1

1

2

Safety information

DANGER indicates an imminently hazardous situation 

which, if not avoided, will result in death or serious injury
WARNING indicates a potentially hazardous situation 

which, if not avoided, could result in death or serious injury
CAUTION indicates a potentially hazardous situation which, 

if not avoided, may result in minor or moderate injury

Before using the product, please read the safety information thoroughly and use it properly.

Alerts declared in the manual are classified to Danger, Warning and Caution by their criticality

DANGER

WARNING

CAUTION

•  Do not touch or connect any undesirable conductive part to input·output 

terminal since there is a possibility of electric shock.

•  Please do not supply the overload larger than the rating to the output contact 

of the relay.

•  The wire length should be as short as possible from the instrument to the 

electrode.

•  Please use a thick wire as possible between the instrument and the 

electrode.

•  Please do not put the input signal wires and other load wires in the same conduit.

• If the input wire is longer, please use the shielded wire.

•  Please avoid installing a controller in a place where there is steam, dust, 

corrosive gas and water splash.

•  Please install AC power lines in a metal conduit with separating input sensor 

signal wires.

•  Never disassemble, modify, or repair the product. There is a possibility of a 

malfunction, an electric shock, or a risk of fire.

※  Please follow the above contents described in the safety information if not it 

may lead to a product failure.

CAUTION

•  If the user use the product with methods other than specified by the 

manufacturer, there may be bodily injuries or property damages.

•  If there is a possibility of an accident caused by errors or malfunctions of this 

product, install external protection circuit to prevent the accident.

WARNING

Specification

Model

FS-3 A (high sensitivity)

FS-3 A (low sensitivity)

Power supply Voltage

110 V a.c / 220 V a.c 50/60 

Allowable voltage fluctuation range

± 10 % of the power supply voltage

Voltage between the 

electrodes secondary voltage

24 V a.c 

8 V a.c 

Power consumption

Approx. 3.2 VA

Response time

Max 80 

㎳ 

when operating, max 160 

 when returning

Operration resistance between electrodes

0 - approx. 27 

0 - approx. 7 

Return resistance between electrodes

approx. 38  

㏀ - ∞Ω

approx. 15 

㏀ - ∞Ω

Control output

Relay contact output (1c): 250 V a.c   5 A (resistive load)

Insulation resistance

100 

 min (with 500 V d.c mega) electric conduction part and 

exposed non-charged metal part

Dielectric strength

2000 V a.c 50 - 60 

 for 1 min (between the two poles recharging part terminal)

Vibration resistance

10-55 

 (for cycle 1 min) Peak amplitude for 2hrs each in X, Y and Z direction 0.76 

Shock resistance

300 ㎨ 

Life expectancy

Mechanically more than 5 million times (relay type), electrically more 

than 500 thousand times (load resistance)

Ambient temperature

-10 ~ 50 

 (with no icing or condensation)

Ambient humidity

35 ~ 85 % R.H. 

Dimension

[Unit : mm]

 

Regarding the connection of load

 

Internal connection

 Low sensitivity

 High sensitivity

•   Attaching the surge observer 

at the each and of inducible 

load  (motor,  solenoid  and 

etc) just like an image given 

on the right side will restrain 

noise to occur

Connections

 

External connection

(Cautious)    Please  and 
must earth E3 terminal

    Level Switch

 

FS - 3 

       Thank you for purchasing HANYOUNG product.

       Please check whether the product is the exactly same as you ordered. 

       Before using the product, please read this instruction manual carefully.

       Please keep this manual where you can view at any time

 INSTRUCTION MANUAL

ML0201KE120813

1381-3, Juan-Dong, Nam-Gu Incheon, Korea.  
TEL:(82-32)876-4697
FAX:(82-32)876-4696
http://www.hynux.net

Jl. cempaka blok F16, No.02 Delta Silicon II  
Cikarang Bekasi Indonesia
TEL : 62-21-8911-8120~4
FAX : 62-21-8911-8126 

HANYOUNGNUX CO.,LTD

PT. HANYOUNG ELECTRONIC INDONESIA

HEAD OFFICE

INDONESIA

FACTORY

Отзывы: