INSTRUCTIONS R429d

Dec 2003

HA4A MODULAR

PRESSURE REGULATORS

¾" THROUGH 6" PORT

(20 MM THROUGH 150 MM)

Specifications, Applications,

Service Instructions & Parts

Various Connection

Styles and Sizes

for Refrigerants

MATERIAL SPECIFICATIONS

Body:
¾ "   t h r o u g h   4 " :   D u c t i l e   i r o n ,   A S T M   A 5 3 6
5" & 6": Cast steel, ASTM A352 LCB
Adapter: Ductile iron, ASTM A536
Piston: Steel, disc type, Teflon piston seal
V-Port/Seat: ductile iron, with Teflon seat
Main Seat: ¾" through 1¼": integral ductile iron
1½" through 6": stainless steel, removable
Gaskets: Nonasbestos, graphite composite
Manual Opening Stem: Steel, plated
Pilots: Stainless steel trim
Pilot Orifice: Stainless steel
Flanges: Forged steel, ASTM A105
Safe Working Pressure: 400 psig (27 bar)
Operating Temperature: –60F to +240F (–50°C to
+115°C), lower temperatures possible at pressure
downratings

INTRODUCTION

These advanced-design, strong-bodied, precision-
manufactured MODULAR regulators are superior in
their ability to overcome dirt and sticky oil during opening
and tight closing. Models are available for nearly every
control function requirement of industrial ammonia and
commercial halocarbon refrigeration.  These regulators
are ideal for cold storage plants, poultry plants, meat
packing, fish processing, freezers, ice plants, breweries,
bottling plants, heat recovery units, petrochemical plants,
pharmaceutical plants, supermarkets, and many others.

APPLICATIONS

Evaporator Pressure Control

Defrost Pressure Control

Condensing Pressure Regulation

Receiver Pressure Control

Hot Gas Bypass Capacity Regulation

Suction Pressure Control

Air or Liquid Temperature Regulation

Internal System Pressure Relief

ADDITIONAL FEATURES

Tolerant of Dry Systems
For Ammonia, R22, R134a and other Hansen-Approved
Refrigerants
Wide Range of Options
Inlet, Outlet, or Differential Pressure
Wide Pressure Ranges
Electric Shut-Off, Dual, or Wide-Opening Available
Safe Working Pressure: 400 psig (27 bar)
CSA Certified, CRN for Canada

INSTALLATION

Regulators should be protected from dirt and moisture
during storage. The arrow on the body should be in the
normal direction of refrigerant flow. 

These valves will

not prevent reverse flow; 

use check valves where

necessary. Regulators are normally in horizontal pipe
lines with pilots and manual-opening stems on top. Do
not rotate the position of the valve adapter or the valve
will not operate.

The system should be free of dirt, weld slag, and rust
particles. Regulators can be equipped with separate,
close-coupled inlet strainers. No small, hidden, internal
screens are used. Gauges and gauge valves should
be installed on the inlet and outlet to help in system
d i a g n o s i s .   B e c a u s e   o f   t h e   m a n y   r e g u l a t o r   p i l o t
combinations, during installation of a large job, the
regulator nameplates should be checked against piping
drawings to guarantee proper function for each location.
Where pilot solenoid control modules are used, the
nameplate coil voltage should be checked before wiring.
Pipe sizing, anchoring, valve rating, system design,
and other precautionary factors should be taken into
consideration to ensure “liquid hammer” will not occur
when the valve opens or closes.

The 5" and 6" valves are type HA4W with integral butt
weld end only. These steel-bodied regulators are
directly welded into the pipe line. During welding, the
manual-opening stem should be opened downward
several turns to protect the Teflon seat from weld heat.

Welds should be annealed as necessary in accordance
with good practice. Painting of valves and welds is
recommended for corrosion protection. Pipe covering,
where applied, should have proper moisture barrier.
Before putting valves into service, all pipe connections,
valve seats, cover seals, and stem seals should be
tested for leaks at pressure levels called for in appropriate
codes.

Содержание HA4A

Страница 1: ...Pressure Wide Pressure Ranges Electric Shut Off Dual or Wide Opening Available Safe Working Pressure 400 psig 27 bar CSA Certified CRN for Canada INSTALLATION Regulators should be protected from dirt...

Страница 2: ...se a 3 8 male hexagon wrench to loosen the four adapter bolts proceeding slowly to avoid refrigerant which may still remain in the valve If piston parts are stuck remove the 2 hex bottom cap in order...

Страница 3: ...the main valve seat to open and regulate flow Hansen regulators are normally furnished with control modules pilots installed and tested see page 3 However modular regulators less pilots and flanges a...

Страница 4: ...s wide to allow pressure to enter the space on top of the piston This causes the main valve seat to open and relieve the inlet pressure provided the outlet pressure is at least 2 psi 0 14 bar lower A...

Страница 5: ...piston which forces the main valve seat to open wide to permit flow in the direction of arrow ADJUSTMENT With solenoid control module de energized follow adjustment procedures for the HA4A Standard R...

Страница 6: ...pressure setting or counterclockwise to lower the inlet pressure setting When the desired refrigerant pressure setting is achieved tighten the adjustment locking nut A final adjustment should be made...

Страница 7: ...8 5 6 7 6 1 6 4 7 9 8 1 1 0 7 1 2 3 4 1 5 0 2 1 2 5 2 1 4 1 9 5 3 9 6 2 8 6 8 3 4 1 1 1 1 0 5 1 1 8 3 7 0 4 1 7 5 3 6 0 8 5 0 2 INSTALLATION DIMENSIONS 1 THROUGH 4 REGULATORS THROUGH 1 REGULATORS M Ad...

Страница 8: ...FOR SERIES AND PARALLEL ARRANGEMENT AD SI solenoid SII P pressure pilots FOR SERIES ARRANGEMENT AS SI solenoid SII pressure pilot 5 AND 6 PILOT PIPING TOP VIEW E Z I S T R O P A T 5 5 2 1 5 0 5 8 2 1...

Страница 9: ......

Отзывы: