background image

8

3.0  MAINTENANCE

3.1 Condenser coil

A.

Air-cooled - clean off accumulated dust and dirt monthly. A
factory mounted blow gun is provided for this purpose.

B.

Water-cooled - clean strainer monthly, more often if
required. Shut off water, remove small plug to relieve
pressure, then remove large plug to remove strainer. Clean
strainer and replace.

3.2 Moisture separator/Oil filters

A.

When to replace the Separator/Filters

Replace filter element when pressure drop across dryer is
excessive or annually.

Dryers have the option of one or two stages of filtration.
The direction for servicing the top stage applies to both the
top stage in a two-stage arrangement and the single stage
in a single stage dryer.

When removing liquids at rated flow conditions, the
pressure drop will be 5 psi (0.35 bar), or less, across the
entire dryer.  An increase in pressure drop will occur only
as the separator/filter elements become loaded with solid
particles.  It is recommended, for maximum filtration
efficiency, the separator/filter elements be replaced when
the pressure drop across the dryer exceeds 10 psi (0.7
bar), or every 12 months, whichever occurs first.

B.

Description of the Separator/Filter Assembly

The separator/filter assembly consists of: the separator
shell assembly (1), the upper shell cap (2), the upper shell
coupling  and gasket (3), the upper piping coupling and
gasket (4), the element retainer plate (5), and the separa-
tor/filter elements (6).

C.

Replacement of the Separator/Filters

  Depressurize the unit before servicing. Failure

to do this may result in injury. The unit must be depressurized
before the couplings are removed.

a.

For normal element replacement, the only assembly
component that must be removed is the upper shell
cap. Remove the insulation from the upper shell cap.

  Check to be sure the unit is depressurized.

b.

Remove the two bolts on the upper shell coupling (3)
and the upper piping coupling (4). Remove the
couplings, exposing the gaskets.

c.

Slide the upper piping gasket up on to the upper
piping. Slide the upper shell gasket down on to the
separator shell (1). The upper shell cap (2) should now
be free and removable.

d.

Remove the upper shell cap (2).

e.

Remove the element retainer plate (5).

f.

Remove the separator/filter elements (6) by simply
lifting them off of the element sealing posts (1b).
Discard the old elements.

g.

Inspect the inside surfaces of the separator shell (1),
the element seal plate (1a), and the element sealing
posts (1b).

NOTE: If the inside surfaces require additional cleaning or
inspection, the entire shell assembly (1) can be removed by
disassembling the lower shell coupling and gasket.

h.

Lubricate the new separator/filter element o-ring seals
according to the element package instructions.

i.

Install the new elements by carefully pushing them on
to the element sealing posts (1b).

j.

Reinstall the element retainer plate (5).

k.

Replace the upper shell cap (2).

l.

Inspect the upper shell cap gasket and the upper
piping gasket and apply a thin coat of lubricant to the
outside and to the sealing lips of these gaskets.

m. Slide the gaskets into position, centering them

between the coupling grooves.

n.

Replace the upper shell cap coupling (3) and the
upper piping coupling (4). Tighten the bolts evenly and
alternately.

  Uneven tightening may cause the gaskets to

pinch and not seal! Gasket damage may result!

o.

Reinstall the insulation.

p.

Slowly repressurize the dryer.

q.

Inspect the assembly for air leaks.

NOTE:  Further disassembly is not required or recommended
for maintenance.

Gasket

Coupling
Half

Grooved Shell

Grooved Upper 
Shell Cap

Bolts

3 & 4

Содержание HPRP 1000

Страница 1: ...MAINTENANCE 8 SIZING 9 ELECTRICAL SCHEMATICS 10 DIMENSIONS AND WEIGHT 14 ENGINEERING DATA 15 TROUBLESHOOTING GUIDE 16 PARTS LIST AIR COOLED UNITS 17 PARTS LIST WATER COOLED UNITS 18 WARRANTY 20 SERVI...

Страница 2: ...weather Damage to electrical and control components may result IMPORTANT WATER COOLED UNITS If unit is shut down below freezing temperatures the water cooled condenser may freeze and cause permanent d...

Страница 3: ...ntilated area Avoid locations immediately adjacent to cold exterior windows or walls or adjacent to high tem perature ovens or boilers D Clearances Free air flow Models 1000 to 1500 Front 24 inches 61...

Страница 4: ...At installation install the petcock on the bulkhead fitting for the manual drain For manual draining convenient dryer depressurization and EDD service a three way valve at the bottom of the moisture s...

Страница 5: ...c Use the Up and Down arrow buttons to set year 00 to 99 representing 2000 to 2099 Press Enter to accept new value d Use the Up and Down arrow buttons to set month three letter abbreviation Press Ent...

Страница 6: ...slowly 5 Close air bypass valve 6 Dryer may be operated in Manual or scheduled modes NOTE Check for correct phasing of unit On air cooled models check fan rotation air must be pulled through the conde...

Страница 7: ...to discharge f Check drain operation push Drain push to test button to energize electric drain A flow of condensate and or air should be present at the drain outlet E Using the RS 232 port The RS 232...

Страница 8: ...t that must be removed is the upper shell cap Remove the insulation from the upper shell cap Check to be sure the unit is depressurized b Remove the two bolts on the upper shell coupling 3 and the upp...

Страница 9: ...INLET INLET TEMPERATURES PRESSURES 80 F 90 F 100 F 110 F 120 F psig kgf cm2 27 C 32 C 38 C 43 C 49 C 50 3 5 1 35 1 05 0 84 0 69 0 56 80 5 6 1 50 1 17 0 95 0 79 0 66 100 7 0 1 55 1 23 1 00 0 82 0 70 12...

Страница 10: ...OR SPECIFIC WIRING INFORMATION 3 SCROLL COMPRESSORS REQUIRE PROPER PHASING SEE COMPRESSOR DATA PLATE FOR CORRECT WIRING SEQUENCE 4 WIRES 55 AND 56 ARE JUMPERED TOGETHER ON STANDARD DRAIN PKG COMPRESSO...

Страница 11: ...AND FAN THERMAL OVERLOADS ARE REMOVED 2 SEE FAN NAMEPLATE FOR SPECIFIC WIRING INFORMATION 3 SCROLL COMPRESSORS REQUIRE PROPER PHASING SEE COMPRESSOR DATA PLATE FOR CORRECT WIRING SEQUENCE 4 WIRES 55 A...

Страница 12: ...RING INFORMATION 3 SCROLL COMPRESSORS REQUIRE PROPER PHASING SEE COMPRESSOR DATA PLATE FOR CORRECT WIRING SEQUENCE 4 WIRES 55 AND 56 ARE JUMPERED TOGETHER ON STANDARD DRAIN PKG FAN1 NOTE 1 2 FAN3 2000...

Страница 13: ...9 10 11 20 21 19 16 17 18 34 35 15 TB2 TC TC 15 16 17 18 20 21 9 10 11 12 13 14 26 27 28 FILTER MONITOR COALESCING RJ 11 FILTER MONITOR RJ 11 WEB MONITOR RS232 PORT LOCAL REMOTE REMOTE STOP START CUST...

Страница 14: ...1250 4 85 2159 48 1207 49 1232 1 740 789 1500 4 1 850 839 1750 6 2 000 907 2000 6 85 2159 54 1372 56 1422 2 100 953 2500 6 2 238 1015 3000 6 2 263 1027 NOTE Dimension and weights are for reference on...

Страница 15: ...98 130 125 150 175 Minimum Circuit Ampacity 16 73 17 42 19 30 28 17 28 44 27 53 32 41 Branch Circuit Fuse Size amps 25 25 30 45 45 45 50 Watts 35 F Evaporator 100 F Ambient 7 850 9 223 9 777 12 621 10...

Страница 16: ...y a Faulty compressor contactor b Faulty N O auxiliary contact on compressor contactor a Faulty compressor contactor b Faulty N C auxiliary contact on compressor contactor a Temperature sensor or wiri...

Страница 17: ...1 4 1 3 8 3 1 0 3 1 4 1 3 8 3 1 0 3 1 4 1 3 8 3 1 0 3 1 4 1 3 8 3 1 0 3 1 4 1 3 8 3 1 0 3 1 4 1 3 8 3 1 0 3 1 4 h c t i w S e r u s s e r P t n a r e g i r f e R h g i H 8 2 8 3 1 0 3 1 4 8 2 8 3 1 0...

Страница 18: ...L 1 3 8 3 1 0 3 1 4 1 3 8 3 1 0 3 1 4 1 3 8 3 1 0 3 1 4 1 3 8 3 1 0 3 1 4 1 3 8 3 1 0 3 1 4 1 3 8 3 1 0 3 1 4 1 3 8 3 1 0 3 1 4 h c t i w S e r u s s e r P t n a r e g i r f e R h g i H 5 3 8 3 1 0 3...

Страница 19: ...19 NOTES...

Страница 20: ...product or part THE FOREGOING WARRANTY IS EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES WHETHER WRITTEN ORAL OR STATUTORY AND IS EXPRESSLY IN LIEU OF THE IMPLIED WARRANTY OF MERCHANTABILITY AND THE I...

Отзывы: